TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.10 SCOPE
Section 215.10 Scope
a) This
standard is intended to apply to the design, construction, repair, alteration,
location, installation and operation of agricultural anhydrous ammonia systems,
including refrigerated ammonia storage systems, noncommercial (including
on-farm) storage and handling systems, and ethanol plants.
b) This
standard does not apply to:
1) any
facility manufacturing anhydrous ammonia and associated storage vessels on site;
2) refrigeration
systems where ammonia is used solely as a refrigerant;
3) ammonia
transportation pipelines;
4) ammonia
barges and tankers; and
5) anhydrous
ammonia used in power generation plants.
c) Railroad
car tanks permanently mounted and used for the storage of anhydrous ammonia
shall be removed from service no later than December 1, 2025.
d) Compliance
with the requirements of this Subpart shall be achieved through repairs and
modifications on or before December 31, 2020.
e) Any
storage vessel that does not have a legible data plate or supporting
documentation of the information on the data plate shall be removed from
service if it is decommissioned from the current site.
(Source: Amended at 40 Ill.
Reg. 8704, effective July 1, 2016)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.15 DEFINITIONS
Section 215.15 Definitions
"Actuation device"
means a mechanical device that is manually activated to cause the closing of emergency
shutoff valves or internal valves stopping the flow of the product in the
system.
"Alteration" means a
change in any item described in the original manufacturer's data report that
affects the pressure-containing capability of the container. Rerating a
container by increasing maximum allowable working pressure or by increasing or
decreasing allowable working temperature shall be considered an alteration.
"Ammonia or anhydrous
ammonia" means the compound formed by the chemical combination of the
elements nitrogen and hydrogen in the molar proportion of one part nitrogen to
three parts hydrogen. This relationship is shown by the chemical formula, NH3.
On a weight basis, the ratio is 14 parts nitrogen to three parts hydrogen or
approximately 82% nitrogen to 18% hydrogen. Ammonia may exist in either
gaseous, liquid or solid state. It is not to be confused with aqua ammonia
(ammonium hydroxide), which is a solution of ammonia in water.
"Approved" means
listed by a recognized testing laboratory, recommended by the manufacturer as
suitable for use with anhydrous ammonia and so marked or documented, or accepted
by the authority having jurisdiction.
"Appurtenance" refers
to all devices such as pressure relief devices, liquid level gauging devices,
valves, pressure gauges, pressure regulators, fittings, metering or devices
designed to be attached to an ammonia container.
"Back check" means a
device that allows liquid or vapor in the vessel, equipment or systems to flow
in only one direction.
"Capacity" means the
total volume of the container measured in standard U.S. gallons unless
otherwise specified.
"Cargo tank" is a bulk
packaging that is:
a tank intended primarily for
the carriage of liquids or gases and includes appurtenances, reinforcements, fittings
and closures;
permanently attached to or forms
a part of a motor vehicle, or is not permanently attached to a motor vehicle
but, by reason of its size, construction or attachment to a motor vehicle, is
loaded or unloaded without being removed from the motor vehicle; and
not fabricated under a
specification for cylinders, portable tanks, tank cars or multi-unit tank car
tanks.
"Cargo tank motor vehicle"
means a motor vehicle with one or more cargo tanks permanently attached to or
forming an integral part of the motor vehicle.
"Certified competent
attendant" means a competent attendant who has successfully completed Certified
Competent Attendant Training.
"Certified grower"
means a grower or grower farm operator who has successfully completed Certified
Grower Training.
"Certified welder"
means any welder who is employed by a company that holds an R stamp certificate
of authentication.
"Chemical splash goggles"
or "goggles" means flexible fitting chemical-protective goggles with
a hooded indirect ventilation system to provide primary protection of the eyes
and eye sockets from the splash of hazardous liquids. Direct vented goggles do
not comply with this definition.
"Commercial" means
buying and selling anhydrous ammonia and/or selling the associated services for
compensation.
"Competent
attendant" means an individual at a commercial or noncommercial site
required to handle, transfer or transport anhydrous ammonia, or otherwise
maintain anhydrous ammonia equipment. The term includes an individual at a
commercial or noncommercial site who makes or breaks connections on anhydrous
ammonia equipment while loading or unloading anhydrous ammonia. The term also
includes custom applicators.
"Container" means all
tanks, except cylinders, as defined in Section 215.15, used for the
transportation or storage of anhydrous ammonia.
"Custom Applicator"
means an individual who applies anhydrous ammonia as an employee of a company
supplying the product or operators for hire.
"Cylinder" means a
pressure vessel designed for pressures higher than 40 psig and having a
circular cross-section. It does not include a portable tank, multi-unit tank
car tank, cargo tank or tank car.
"Decommission" means
to stop using a pressurized vessel and remove it from service.
"Department" means the
Illinois Department of Agriculture, State Fairgrounds, P.O. Box 19281,
Springfield IL 62794.
"Design pressure" is
identical to the term "Maximum Allowable Working Pressure" used in
the ASME Code.
"Emergency shower"
means a shower unit permanently connected to a source of clean water that
enables the user to have water cascading over the entire body.
"Emergency shutoff valve"
or "ESV" means a shutoff valve incorporating a manual means of
closure. All approved ESVs shall incorporate a reliable actuation system that
will close all of the emergency shutoff valves and/or internal valves of the
piping system on the first attempt in the event of an emergency or of testing
from a remote location. An emergency shutoff valve shall remain closed except
during periods of operation.
"Excess flow valve"
means a valve that is designed to close automatically at the rated flow of
vapor or liquid as specified by the manufacturer. The piping, including
valves, fittings and hose, being protected by an excess flow valve shall have a
greater capacity than the rated flow of the protected valve, so the valve will
likely close in case of failure of the delivery system at any point in the line
or fittings.
"Eye wash unit" means
a device used to irrigate and flush the eyes with clean water. Depending upon
the requirements set forth in this standard, the device may be a plumbed unit
permanently connected to a source of clean water, or it may be a self-contained
unit not permanently installed that must be refilled or replaced after use.
"Filling density"
means the percent ratio of the weight of the ammonia permitted in a container
to the weight of water at 60°F (15.6°C) that the container will hold when
full. One pound of water = 27.74 cubic inches (455 ml) at 60°F (15.6°C). For
determining the water capacity of the tank in pounds, the weight of one gallon
(231 cubic inches) (3.785 L) of water at 60°F (15.6°C) in air shall be 8.328 lb
(3.778 kg).
"Grower" means any
individual who produces an agricultural commodity on property he or she owns or
controls.
"Grower
farm operator" means an individual employed by or otherwise authorized
by a grower to transport or apply anhydrous ammonia, or to otherwise maintain
anhydrous ammonia equipment. These individuals include grower family members,
full- and part-time hired help, and others providing anhydrous ammonia services
at no fee.
"Hitching point" means
the point where a mechanical connection is made between the nurse tank and the
tool bar, towing vehicle or another nurse tank.
"Hydrostatic relief valve"
means a pressure relief device for liquid service designed to prevent excessive
pressure due to thermal expansion when a pipe or hose is filled with liquid
such as between block valves or blinds.
"Immediately Dangerous to
Life or Health" or "IDLH" means the maximum concentration from
which unprotected persons are able to escape within 30 minutes without
escape-impairing symptoms or irreversible health effects. The IDLH for ammonia
is 300 ppm by volume in accordance with the NIOSH Pocket Guide to Chemical
Hazards.
"Implement
of husbandry", for the purpose of this Part, means a system that includes
a nurse tank with a capacity of 3000 gallons or less or an application device
used for transporting and/or applying anhydrous ammonia exclusively for
agricultural purposes.
"Institutional occupancy"
means a location where people may be unable to vacate voluntarily and shall be
deemed to include nursing homes, hospitals, jails and schools.
"Internal valve" means
a storage container primary shutoff valve that can be closed remotely and
incorporates an internal excess flow valve with the seat and seat disc located
within the container in a manner to remain in place in the event of external
damage to the valve and/or associated piping. An internal valve shall
incorporate a reliable actuation system that will close all of the emergency
shutoff valves and/or internal valves of the piping system on the first attempt
in the event of an emergency or of testing from a remote location. An
emergency valve shall remain closed except during periods of operation.
"Load" or "loading"
means the transfer of anhydrous ammonia, at a commercial facility or
noncommercial facility, from facility storage to transportation equipment,
application equipment or field nursing transportation equipment.
"Material suitable for use"
includes iron, steel and certain non-ferrous alloys that are compatible for use
in anhydrous ammonia service. Copper, brass, zinc and certain alloys,
especially those containing copper, are not suitable for anhydrous ammonia
service.
"Mechanical secure point"
means a connection point affixed to the nurse tank or running gear for the
attachment of the nurse tank hoses. The mechanically secure point provides
resistance allowing the breakaway coupler to operate in the event of detachment
of the nurse tank from the towing implement.
"New facility" means
an approved location or a facility that has not been previously approved for
the storage and handling of anhydrous ammonia.
"Temporary Certified
Competent Attendant" means a person who has successfully completed a Department
approved online training course and received a certificate of completion. The
certificate will expire on July 15 or December 31 as indicated on the
certificate and cannot be repeated or renewed.
"Noncommercial facility"
means a site, including the land and structures, and the equipment fixed on the
land and structures, designed and used for the storage and handling of anhydrous
ammonia used in the associated not-for-hire operations.
"Nonmobile" means not
readily capable of moving or being moved from place to place.
"Permanent storage
installation" means a system employing a stationary (fixed) container used
exclusively for storage or supply.
"Personal protective
equipment" means adequate clothing and equipment used to ensure personal
safety in the workplace.
"Positive pressure
self-contaminated breathing apparatus" or "SCBA" means a full
face piece respirator approved by NIOSH/MSHA for respiratory protection for
both entry into or escape from oxygen-deficient atmospheres or a concentration
of gases or vapors that are immediately dangerous to life or health in which
the supply of air is carried by the wearer. The air pressure inside the face
piece is positive in relation to the air pressure of the outside atmosphere
during exhalation and inhalation.
"Pressure relief valve"
is a device designed to open to prevent an increase in internal vapor pressure in
the container in excess of a specified value due to an emergency or abnormal
condition and to close and prevent further flow after normal conditions have
been restored.
"Private assembly"
means a location where people gather together but is not generally open to the
public.
"Protective gloves, boots
and suits" are items made of rubber or other material impervious to
ammonia. Gloves refer to gauntlet-style of sufficient length to allow for
cuffing and that provide thermal protection suitable for ammonia exposure.
"psia" means pounds
per square inch absolute.
"psig" means pounds
per square inch gauge.
"Public assembly" is a
location that includes, but is not limited to, churches, manufacturing
companies, cemeteries currently in operation, land managed for recreational or
conservation purposes, museums, camps, parks, retail and wholesale facilities,
and shopping centers. Examples of public assembly include places that operate
less than 52 weeks per year, such as businesses or other places that experience
seasonal shutdowns and parks, camps and recreational areas that experience
seasonal shutdowns or reduced attendance during a portion of the calendar year,
provided that these places are frequented by at least 50 persons at least once
per week during the portions of the year when seasonal shutdowns or reductions in
attendance do not occur. "Reinstallation" means the removal of a
storage vessel from the originally approved site to a different site.
"Repair" means the
work necessary to restore a container, cylinder or system to a safe and
satisfactory operating condition provided there is, in all cases, no deviation
from the original design. Repairs include the addition or replacement of
pressure or nonpressure parts that do not change the design temperature or
pressure of the container, cylinder or system.
"Reportable quantity" or
"RQ" means the federal RQ (Reportable Quantity) for an anhydrous
ammonia release, which is 100 lb. (45 kg) or 18 gallons (68 litres).
"Respirator" means an
air-purifying device with full face piece and either chin-style or front- or
back-mounted canisters with associated connections approved by NIOSH for use in
ammonia contaminated atmosphere in compliance with 29 CFR 1910.134 and selected
in accordance with ANSI Z88.2. A respirator of the air-purifying type must be
used only in an atmosphere containing 19.5% to 22.0% oxygen by volume.
"Responsible party"
means the individual, partnership, corporation or association in control of the
anhydrous ammonia at the time of an accident or incident involving an RQ
release.
"System" means an
assembly of equipment consisting essentially of the containers, hoses,
appurtenances, pumps, compressors and interconnecting piping.
"Tank" means a vessel
designed and constructed for the storage and handling of anhydrous ammonia.
"Tool bar" means an implement
of husbandry for the field application of ammonia that is used in conjunction
with nurse tanks. For purposes of this definition, chisel plows, field
cultivators or other conventional tillage equipment that has been manufactured
or retrofitted with any ammonia valves, gauges, hoses, application knives,
metering devices, safety devices or tool bar refrigeration units for the
purpose of ammonia application are considered to be tool bars.
"Tool bar breakaway
device" means a self-closing device designed to disconnect anhydrous
ammonia hoses upon detachment from the nurse tanks.
"Tool bar refrigeration
unit" means a unitized system of ammonia pipe, valves and gauges, with
ammonia monitoring, handling, metering and manifold-dispensing devices that are
used to process pressurized ammonia into refrigerated ammonia for more accurate
metering and distribution during field application.
"Unload" or
"unloading" means the transfer of anhydrous ammonia at commercial or
noncommercial facilities from the transport vehicle into facility storage.
"UN 1005" means the
placard number assigned to anhydrous ammonia by the United Nations Committee of
Experts on the Transportation of Dangerous Goods.
"Wet hose" is an
anhydrous hose with shutoff valves at each end that is capable of containing
liquid product at all times.
(Source: Amended at 44 Ill.
Reg. 18281, effective October 29, 2020)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.16 INCORPORATED AND REFERENCED MATERIALS
Section 215.16 Incorporated and Referenced Materials
a) The following
regulations and standards are incorporated in this Part:
1) Private
and Professional Association Standards
A) The
American National Standards Institute (ANSI), 25 West 43rd Street, 4th
Floor, New York NY 10036
ANSI Z88.2
Practices for Respiratory Protection (2015)
B) The
American Petroleum Institute (API or API-ASME), 15 Inverness Way East,
Englewood CO 80112
i) Code
for Unfired Pressure Vessels for Petroleum Liquids and Gases of the American
Petroleum Institute and the American Society of Mechanical Engineers (API-ASME)
(sometimes known as the API-ASME Code) (The API-ASME Code, as a joint
publication and interpretation service, was discontinued after 1956, and
construction of containers to the API-ASME Code has not been authorized since
1961.)
ii) API
510 – Pressure Vessel Inspection Code: In-Service Inspection, Rating, Repair
and Alteration (2014) (After discontinuance of the API-ASME Code (see
subsection (a)(1)(B)(i)), a need was seen to assure uniform maintenance and
inspection practices continued, which led to the issuance of API 510 beginning
in 1958 (available as stated in subsection (a)(1)(B)(i)).)
iii) The
Unfired Pressure Vessel Code of the American Society of Mechanical Engineers
(Sec. VIII of the ASME Boiler Construction Code), including editions through
1981, or the Joint Code of the American Petroleum Institute and the American
Society of Mechanical Engineers (API-ASME Code), including editions through 1981
iv) API
12-C – Specification for Welded Oil Storage Tanks (1958)
v) API
Standard 620 (2013) (including addendum 1, 2014), Design and Construction of
Large, Welded, Low-Pressure Storage Tanks (including Tables 2.02, R.2.2, R.2.3
or R.2.4 and Appendix R)
C) The
American Society of Agricultural and Biological Engineers (ASABE/ASAE), 2950
Niles Road, St. Joseph MI 49085
i) ASABE/ASAE S276.5
(2003)
ii) ASABE/ASAE
S338.2 (2006) Field Equipment for Agriculture-Safety Chain for Towed Equipment
D) The
American Society of Mechanical Engineers (ASME), Two Park Avenue, New York NY
10016-5990
i) ASME B31.3 Process
Piping (2014)
ii) ASME
B31.5 Refrigeration Piping and Heat Transfer Components (2013)
iii) U-68
and U-69 ASME Code Containers refer to the ASME Boiler and Pressure Vessel Code
of the American Society of Mechanical Engineers (1949), Section VIII,
paragraphs U-68 and U-69
iv) UG-125
through UG-136 refer to the ASME Boiler and Pressure Vessel Code of the
American Society of Mechanical Engineers (1949), Section VIII, Division 1,
paragraphs UG-125 through UG-136
v) U-200
or U-201 refers to the ASME Boiler and Pressure Vessel Code of the American
Society of Mechanical Engineers (1949), Section VIII, paragraphs U-200 or U-201
vi) UW-12
is a table in Section VIII, Division 1, of ASME BPBC – viii-1 (2015)
E) American
Society for Testing and Materials (ASTM), 100 Barr Harbor Drive, PO Box C700,
West Conshohocken PA 19428-2959
i) ASTM
A47 – Standard Specification for Ferritic Malleable Iron Castings (2014)
ii) ASTM
A53 – Standard Specification for Pipe, Steel, Black and Hot-Dipped,
Zinc-Coated, Welded and Seamless (2012)
iii) ASTM
A395 – Standard Specification for Ferritic Ductile Iron Pressure-Retaining
Castings for Use at Elevated Temperatures (2014)
iv) Section
IX, Welding Qualifications refers to the ASME Boiler and Pressure Vessel Code,
IX, Qualification Standard for Welding and Brazing Procedures, Welders,
Brazers, and Welding and Brazing Operators, Welding and Brazing Qualifications
(2010)
F) The
Association for Rubber Product Manufacturers (ARPM), 7321 Shadeland Station
Way, Suite 285, Indianapolis IN 46256
ARPM IP-14, Specifications for
Anhydrous Ammonia Hose (2003, reaffirmed 2009)
G) The
Compressed Gas Association (CGA), 14501 George Carter Way, Suite 103, Chantilly
VA 20151
i) CGA G-2 – Anhydrous
Ammonia (1995)
ii) CGA
G-2.1 – Safety Requirements for the Storage and Handling of Anhydrous Ammonia
(2014)
iii) CGA
P-7 – Standard for Requalification of Cargo Tank Hose Used in the Transfer of
Carbon Dioxide Refrigerated Liquid (2007)
H) The
National Board of Boiler and Pressure Vessel Inspectors (NBBI), 1055 Crupper
Avenue, Columbus OH 43229-1183
National Board
Inspection Code (2015)
I) The
National Fire Protection Association (NFPA), 25 West 43rd Street, 4th
Floor, New York NY 10036
NFPA 70: National
Electrical Code (2014)
J) The
Underwriters Laboratory (UL), 47173 Benicia Street, Fremont CA 94538
UL-132, Standard on Safety Relief
Valves for Anhydrous Ammonia and LP Gas (2015)
2) Federal
Regulations
A) 29 CFR 1910.134 (2016)
B) 49 CFR 105-180 (2015)
i) subchapter
A, sections 105-110, Hazardous Materials and Oil Transportation
ii) subchapter B, section
130, Oil Transportation
iii) subchapter
C, sections 171-180, Hazardous Materials Regulations
● 49 CFR 173.315(m)(1)(v) (2015)
Compressed gases in cargo tanks and portable tanks
● 49 CFR 177.834(a) through (j)
(2016), Loading and unloading
● 49 CFR 177. 840 (2015), Class 2
(gasses) materials
3) Federal
Government Publications
The National Institute for
Occupational Safety and Health (NIOSH), NIOSH Pocket Guide to Chemical Hazards,
GPO stock number 017-033-00500-1, available from the Government Printing
Office, Washington DC 20402-9325
Enforcement Response Policy For Sections
302, 304, 311 and 312 of the Emergency Planning and Community Right-to-Know Act
and Section 103 of the Comprehensive Environmental Response, Compensation and Liability
Act, available from the Office of Regulatory Enforcement, Office of Enforcement
and Compliance Assurance, United States Environmental Protection Agency,
September 30, 1999
b) All
incorporations by reference of federal regulations and guidelines and the
standards of nationally recognized organizations refer to the regulations,
guidelines and standards on the dates specified and do not include any
amendments or editions subsequent to the date specified.
c) The following State statutes
and administrative rules are referenced in this Part:
1) State of Illinois
Statutes
Weights and
Measures Act [225 ILCS 470]
Illinois
Emergency Management Agency Act [20 ILCS 3305/5(c)]
2) Illinois Department of
Agriculture Rules
A) 8 Ill.
Adm. Code 1, Administrative Rules (Formal Administrative Proceedings; Contested
Cases; Petitions; Public Disclosure)
B) 8 Ill. Adm. Code 600,
Weights and Measures Act
C) 8 Ill. Adm. Code 255,
Agrichemical Containment
(Source: Amended at 44 Ill. Reg. 18281,
effective October 29, 2020)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.20 SAFETY
Section 215.20 Safety
a) All
competent attendants shall be certified to understand the properties of
ammonia, to become competent in safe operating practices, and to take
appropriate actions in the event of a leak or an emergency. Certified
competent attendant training programs shall be approved by the Department every
3 years.
1) Certified
competent attendants shall complete an attendance-based or temporary online
certified competent attendant training approved by the Department or an
equivalent training program approved by the Department.
2) Certification shall be for a period of 3 years
and refresher training shall be at least every 3 years. Documentation of
completed training shall be maintained by the certified competent attendants or
their employer.
3) Any
person who conducts anhydrous ammonia safety training to certify individuals as
certified competent attendants shall:
A) Be
a certified competent attendant by attending a Department-sponsored certified
competent attendant training program annually;
B) Train
with a Department-approved training program and associated materials; and
C) Submit
to the Department a roster of individuals trained, including their name,
company name, home address, company address and date of training.
4) Any
person or entity who conducts online temporary certified competent attendant
training shall submit a roster of individuals trained, with their name, company
name, company address and date of the training. The online temporary training program
shall be approved by the Department and reapproved every 3 years.
b) Persons
involved with the loading or unloading of anhydrous ammonia as defined in this
Subpart, into permanent storage vessels from cargo tanks shall satisfy the
safety requirements of this Section if they meet USDOT transportation
regulations and are not subject to the requirements of a certified competent
attendant.
c) Persons
at commercial facilities that hold a current USDOT Special Permit issued by the
Pipeline and Hazardous Material Safety Administration pertaining to loading and
unloading operations are not subject to the requirements of a certified
competent attendant.
d) All
growers or grower farm operators who transport or apply anhydrous ammonia, or
otherwise maintain anhydrous ammonia equipment, shall be certified to
understand the properties of ammonia, to become competent in safe operating
practices, and to take appropriate actions in the event of a leak or an
emergency. Initial certification shall be achieved no later than April 1,
2022.
1) Certified
grower training shall be offered at no cost to the grower or grower farm
operator via the attendance-based or online training program available on the
Department's website.
2) Certification
shall be for a period of 3 years and refresher training shall be at least every
3 years. Documentation of completed training shall be maintained by the grower
or grower farm operator.
3) The
attendance-based and on-line certified grower training program shall be
reviewed and approved by the Department every 3 years.
4) Any
person who conducts certified grower training shall:
A) Qualify as a certified competent attendant by
attending a Department-sponsored certified competent attendant training program
annually;
B) Train using
the Department-approved training program and associated materials; and
C) Submit
to the Department a roster of individuals trained, including their name, home
address and date of training.
5) The
Department will record the names, home addresses, and date of training of
individuals who completed certified grower training.
e) All
permanent storage installations shall have on hand, at minimum, the following
equipment for safety and emergency purposes:
1) One
full-faced respirator with one spare ammonia canister that has not exceeded its
expiration date in a readily accessible location. A self-contained breathing
apparatus (SCBA) can meet this requirement only when the facility is trained in
accordance with OSHA for rescue or emergency response to a release as defined
by OSHA.
2) One
pair of protective gloves impervious to anhydrous ammonia.
3) One
pair of protective boots impervious to anhydrous ammonia.
4) One
protective slicker and/or protective pants and jacket, all impervious to
anhydrous ammonia.
5) Chemical
splash goggles.
6) An
easily accessible emergency shower and a plumbed eyewash unit or at least 150
gallons of clean potable or potable quality water in a single open top
container that is readily accessible.
f) Each
cargo tank transferring agricultural anhydrous ammonia, except an implement of
husbandry, shall carry:
1) At
least 5 gallons of clean water in a container designed to provide ready access
to the water for flushing any area of the body contacted by ammonia.
2) One
pair of protective gloves impervious to ammonia.
3) One
full-faced respirator with one spare ammonia canister, in a readily accessible
location, that has not exceeded its expiration.
4) Chemical
splash goggles.
g) Releases over the RQ amount, unless otherwise permitted by
law, require the responsible party to make certain immediate notifications,
which include the local emergency response system (911), National Response
Center (NRC), State Emergency Response Commission (SERC), and the Local
Emergency Planning Committee (LEPC).
(Source: Amended at 44 Ill.
Reg. 18281, effective October 29, 2020)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.25 BASIC RULES
Section 215.25 Basic Rules
This Section applies to all Sections
of this Part unless otherwise noted.
a) These
provisions shall not be construed as prohibiting the continued use or
reinstallation of containers constructed and maintained in accordance with the
1949, 1950, 1952, 1956, 1959, 1965, 1968, 1971, 1974, 1977, 1980, 1983, 1986,
1989, 1992, 1995 and 1998 editions of the ASME Code or any revisions thereof in
effect at the time of fabrication. Reinstalled stationary pressure vessels with
a design capacity greater than 3000 gallons shall comply with CGA G-2.1,
Section 5.1. If a storage tank is currently being used and does not have a
U-1A form or a build sheet or a legible data plate, it must be taken out of
service by January 1, 2030.
1) Containers
in use or operation on or after July 1, 2016, and any storage vessel that is
not in service within the State of Illinois, or any storage vessel greater than
3000 gallons to be reinstalled, shall comply with one or more of the following:
A) The
storage vessel has been stress relieved during fabrication in accordance with
the Code in effect at the time of fabrication; or
B) The
storage vessel has cold-formed heads that have been heat stress relieved; or
C) The
storage vessel has been fabricated with hot-formed heads.
2) Welded
attachments to pads may be made after post-weld heat treatment. However,
implements of husbandry do not require post-weld heat treatment if they are
fabricated with hot-formed heads or with cold-formed heads that have been
stress relieved.
b) Requirements
for new construction and original test, repair, and alterations of containers
(including USDOT portable tanks), other than refrigerated storage tanks must
comply with the following:
1) Containers
used with systems covered in Sections 215.85, 215.110, and 215.115 shall be
made of steel or other material compatible with ammonia and tested in
accordance with the currently incorporated ASME Code (see Section 215.16). An
exception to the ASME Code requirements is that construction under Table UW 12
at a basic joint efficiency of under 80% is not authorized.
2) Containers
designed and constructed in accordance with the ASME Code, other than
refrigerated storage containers, shall comply with the following additional
requirements:
A) The
entire container shall be postweld heat treated after completion of all welds
to the shells and heads. The method employed shall be as prescribed in the
ASME Code, except that the provisions for extended time at a lower temperature
for postweld heat treatment shall not be permitted. Welded attachments to pads
may be made after postweld heat treatment. Exception: implements of husbandry
will not require postweld heat treatment if they are fabricated with hot-formed
heads or with cold-formed heads that have been stress relieved.
B) Steels
used in fabricating pressure containing parts of a container shall not exceed a
specified tensile strength of 70,000 psi. Exception: implements of husbandry
may be fabricated from steel having a specified tensile strength of 75,000 psi.
C) Containers
shall be inspected by a person who holds a valid National Board Commission.
Exception: refrigerated storage tanks with a design pressure of 15 psig or less
and containers covered in Section 215.90.
D) Repair
or alteration of pressure-containing parts of a container shall be performed in
compliance with the applicable provisions of the current edition of the
National Board Inspection Code. Where specific procedures are not given, it is
intended that, subject to acceptance of the inspector, all repair or alteration
shall conform as much as possible to the ASME Code section and edition to which
the container was constructed.
c) Except
for pneumatic testing, all containers shall only be pressured with ammonia
vapor except for dual usage involving the storage of liquid propane. Any
device used for the introduction of atmospheric air into any part of anhydrous
ammonia storage, transportation or application systems is prohibited. Any
introduction of any substance other than anhydrous ammonia into the closed loop
anhydrous ammonia system shall be approved by the Department prior to
implementation, except when required to comply with the ASME Code or USDOT
regulations.
d) Any
firm that completes any repair or alteration to a pressure vessel or any piping
and associated appurtenances shall be performed by a firm that holds a valid
certificate of authorization, commonly referred to as an R stamp holder.
e) A
written record of all inspections and maintenance shall be kept at the facility
for a period of 5 years or until sold or removed from service.
f) Railroad
car tanks permanently mounted and used for storage of anhydrous ammonia shall
be removed from a service no later than December 1, 2025.
g) Compliance
with the requirements of this Subpart shall be achieved through repairs and
modifications on or before December 31, 2020.
h) Any
storage vessel that does not have a legible data plate or supporting
documentation of the information on the data plate shall be removed from
service if it is decommissioned from the current site.
(Source: Amended at 40 Ill. Reg. 8704,
effective July 1, 2016)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.30 LOCATION OF STORAGE TANKS
Section 215.30 Location of
Storage Tanks
a) Tanks
shall be located outside of buildings unless the building is especially
constructed for the safe handling and storage of anhydrous ammonia. Permanent
storage shall be located outside of densely populated areas and subject to the
approval of the Department as follows: If located within the corporate limits
of a village, town, or city, written approval of the municipality's governing
body or a county zoning permit shall be submitted to the Department before
tentative approval to begin construction of a permanent storage facility will
be given. The intended storage must be completed and approved by the
Department within one year from the date written tentative approval was given.
Final approval will be given if the facility and equipment complies with this
Part.
b) Containers
shall be located at least 50 feet from a dug well or other source of potable
water.
c) Nurse
tank load out risers and containers for newly approved sites after July 1, 2003
shall be a minimum distance of 200 feet from the property line. Installation
of additional load out risers or containers at sites approved prior to July 1,
2003 shall be a minimum distance of 75 feet from the property line.
d) Container
locations shall comply with the following distance requirements:
|
|
Minimum Distance
(feet) from Container
|
|
Nominal
capacity of containers (gallons)
|
Railroad
mainline property
|
Place of private
or public assembly
|
Institutional
occupancy
|
|
|
|
|
|
|
001-3000
|
100
|
200
|
750
|
|
over 3000
|
100
|
400
|
1000
|
e) Offices
or buildings integral to the agrichemical business are exempt from the minimum
distance requirement. Excluded from the distance requirement are those
installations installed prior to July 1, 2003. The Department will approve
replacement storage tanks to be installed. A replacement tank may be of a
larger capacity. Replacement tanks must meet all requirements of this Part with
the exception of subsection (d). The provisions concerning replacement of
tanks applies specifically to installations installed prior to July 1, 2003. Notwithstanding
the other provisions of this Section, the Department shall not require evidence
of a county zoning permit or approval of the municipal governing body in the
case of replacement of anhydrous ammonia storage vessels of equal or lesser
static volume.
f) A
nurse tank of not more than 3000 gallons or less than 1000 gallons water
capacity may be used as temporary storage in instances where anhydrous ammonia
is used in the manufacturing of liquid or suspension fertilizers provided that
written approval of the municipality’s governing board or a county zoning
permit shall be submitted to the Department before site approval will be
given. Approval will be given based upon compliance with the requirement of
this subsection (f). The distance of the temporary storage nurse tank shall
not be less than 50 feet from the property line or source of drinking water,
not less than 200 feet from existing places of private or public assembly, or
not less than 750 feet from any place of institutional occupancy. The draw bar
must be securely fastened to an anchoring device so as to render the nurse tank
immovable while being used in the manufacturing of fertilizer. During the time
the site is unattended, all liquid and vapor valves must be plugged or capped.
g) Container
storage areas shall be accessible to emergency vehicles and personnel.
h) Storage
container areas shall be maintained clear of dry grass and weeds and other
combustible materials.
(Source: Amended at 40 Ill.
Reg. 8704, effective July 1, 2016)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.35 MARKINGS OF NON-REFRIGERATED CONTAINERS AND SYSTEMS OTHER THAN DOT CONTAINERS
Section 215.35 Markings of
Non-Refrigerated Containers and Systems other than DOT Containers
a) Each
system nameplate shall be made of a non-corroding metal permanently attached to
the system by continuous welding around its perimeter and located so as to be
readily accessible for inspection. Nameplates shall be maintained in legible
condition and include markings as prescribed.
b) Each
container or system covered in Sections 215.85, 215.90, 215.110 or 215.115
shall be marked as follows:
1) With
a mark identifying compliance with and other markings required by the Code
under which the container is constructed, with the capacity of the container in
pounds or gallons (U.S. Standards), with the working pressure in psig for which
the container is designed, and with the thickness of the shell and heads.
2) With
the name and address of the supplier of the system or the trade name of the
system and the date of manufacture. This information shall appear on the
system nameplate for aboveground containers.
3) With
markings indicating the maximum level to which the container may be filled with
liquid at temperatures between 20°F and 100°F, except on containers provided
with fixed maximum level indicators or that are filled by weighing. Markings shall
be in increments of not more than 20°F and shall appear on the system nameplate
or on the liquid level gauging device on both underground and aboveground
containers. Refrigerated storage tanks shall be exempt from these requirements
but shall be marked to show the maximum permissible liquid level (see Section
215.60).
4) With
the overall length and outside diameter of the container.
c) All
main operating valves on permanently installed storage containers having a
capacity of over 3000 water gallons shall be identified to show whether the
valve is in liquid or vapor service. The method of identification shall be by
label or color code as follows:
1) Label:
The label LIQUID (or LIQUID VALVE) or VAPOR (or VAPOR VALVE), as appropriate,
shall be placed on or within 12 inches of the valve by means of a stencil tag
or decal; or
2) Color
Code: Liquid valves shall be painted orange and vapor valves shall be painted
yellow. The legend ORANGE − LIQUID or YELLOW − VAPOR shall be
displayed in a conspicuous place at each operating point utilized for loading
or unloading at each permanent storage location. The legend shall have letters
at least two inches high and shall be placed against a contrasting background.
d) Containers
manufactured after January 1, 2003 shall bear a National Board of Boiler and
Pressure Vessel Inspectors stamp indicating registration of the container with that
organization.
(Source: Amended at 40 Ill.
Reg. 8704, effective July 1, 2016)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.40 TANK APPURTENANCES
Section 215.40 Tank
Appurtenances
a) All tanks
and appurtenances of each system shall be approved by the Department prior to
initiation of operations, including the receipt of anhydrous ammonia.
b) All
appurtenances shall be designed for no less than the maximum working pressure
of the portion of the system on which they are installed. All appurtenances
shall be fabricated from materials proved suitable for anhydrous ammonia
service.
c) All
connections to containers except connections for pressure relief devices,
thermometer well, liquid level gauging devices, or connections fitted with No.
54 (0.055 inches) drill size orifice or those plugged shall have shutoff valves
located as close to the container as practical.
d) Excess
flow valves or approved systems shall close automatically at the rated flows of
vapor or liquid as specified by the manufacturer. The piping, including valves
and fittings in the same flow path as the excess flow valve, shall have a
greater capacity than the rated flow of the excess flow valve or approved
system.
e) Liquid
level gauging devices that require bleeding of the product to the atmosphere
and that are so constructed that outward flow will not exceed that passed by a
No. 54 (0.055 inches) drill size opening need not be equipped with excess flow
valves.
f) An
opening in a container to which a pressure gauge connection is made need not be
equipped with an excess flow valve if the opening is not larger than No. 54
(0.055 inches) drill size.
g) Each
facility shall provide the minimum protection at each non-refrigerated storage
tank opening utilized for the transfer of product as follows:
1) The
installation of an:
A) internal
valve in the tank with a manual shutoff valve located immediately outside of
the opening; or
B) approved
excess flow valve or a back check valve inside of the tank, a manual shutoff
valve located immediately outside of the opening and an approved emergency shutoff
valve (ESV) located within 3 feet of the opening side of the manual shutoff
valve.
2) Approved
ESVs or internal valves shall incorporate a reliable actuation system that will
close all of the ESVs or internal valves of the piping system on the first
attempt in the event of emergency or of testing from a remote location. A
minimum of 2 remote actuation devices shall be located no less than 25 feet
reasonably opposed to each other.
3) If
using a pressure source for activation of the ESVs or internal valves, nitrogen,
compressed air or carbon dioxide is deemed acceptable. If using compressed air
as a pressure source, the air shall be clean and kept at a moisture level that
will not prevent the system from operating. Propane or other flammable
materials shall be prohibited for use to activate an ESV or an internal valve.
4) ESVs and internal valves shall be tested annually for the
functions required. A record of each test result shall be kept at the facility
for a minimum of 5 years.
h) Excess
flow valves shall be designed with a by-pass, not to exceed a No. 60 (0.040
inches) drill size opening, to allow equalization of pressure.
i) All
excess flow valves shall be plainly and permanently marked with the name or
trademark of the manufacturer, the catalog number, and the rated capacity.
j) Each
filling connection on non-refrigerated containers shall have a positive shutoff
valve in conjunction with either an approved internal back-pressure check valve
or an approved internal excess flow valve. Vapor connections on
non-refrigerated containers shall have a positive shutoff valve together with
an approved internal excess flow.
(Source: Amended at 40 Ill.
Reg. 8704, effective July 1, 2016)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.45 PIPING, TUBING AND FITTINGS
Section 215.45 Piping,
Tubing and Fittings
a) All
piping, tubing and fittings shall be made of steel or other material suitable
for anhydrous ammonia service. Brass, copper or galvanized steel pipe or
tubing shall not be used. Cast iron fittings shall not be used. Those parts
of valves that are subjected to gas pressure shall be made of steel, ductile
(nodular) iron, or malleable iron. Ductile iron shall meet the requirements of
ASTM A395 and malleable iron the requirements of ASTM A47.
b) All
piping, tubing, and fittings shall be designed for a pressure no less than the
maximum pressure to which they will be subjected in service.
c) All
piping shall be supported to prevent damage to the pipes. Provisions shall be
made for expansion, contraction, jarring, vibration and settling. All
refrigeration system piping shall conform to the Refrigeration Piping Code (ASME
B31.5) as it applies to anhydrous ammonia.
d) Piping
used on non-refrigerated systems shall be at least ASTM A53 Grade B seamless or
electric resistance welded pipe. Pipe joints shall be threaded, welded or
flanged. Pipe shall be at least Schedule 40 when joints are welded or welded
and flanged. Pipe shall be at least Schedule 80 when joints are threaded.
Threaded nipples shall be seamless. Welding shall be done by a certified
welder.
e) Metal,
flexible connections may be used for permanent installations to provide for
expansion, contraction, jarring, vibrating and settling. In no case shall the
angle of the connection exceed 15 degrees. The connection used for
non-refrigerated installations shall have a minimum working pressure of 350
psig and a minimum burst pressure of 1750 psig.
f) Adequate
provisions shall be made to protect all exposed piping from physical damage that
might result from impact by moving machinery, automobiles or trucks, or any
other equipment at the facility. Underground piping is allowable.
g) Joint
compounds shall be resistant to ammonia at the maximum pressure and temperature
to which they may be subjected in service.
h) After
assembly, all piping, fittings, and tubing shall be tested and proved to be
free from leaks at a pressure no less than the normal operating pressure of the
system.
(Source: Amended at 40 Ill.
Reg. 8704, effective July 1, 2016)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.50 HOSE SPECIFICATIONS
Section 215.50 Hose
Specifications
a) Hose
used in ammonia service and subject to container pressure shall conform to ARPM
IP-14. Dual usage hoses for propane and anhydrous ammonia shall be prohibited.
b) Hose
subject to container pressure shall be designed for a minimum working pressure
of 350 psig and a minimum burst pressure of 1750 psig. Hose assemblies, when
made up, shall be capable of withstanding a test pressure of 500 psig.
c) Hose
and hose connections located on the low-pressure side of flow control, or
pressure-reducing valves on devices discharging to atmospheric pressure, shall
be designed for the maximum low-side working pressure. All connections shall
be designed, constructed and installed so that there will be no leakage when
connected. Shutoff valves on the end of liquid and vapor transfer hoses shall
be equipped with bleed valves to enable the operator to bleed off pressure
prior to disconnecting the hoses except when using minimum loss valve.
d) When
a liquid transfer hose is not drained of liquid upon completion of transfer
operations, that hose shall be equipped with an approved shutoff valve at the
discharge end. Provision shall be made to prevent excessive hydrostatic
pressure in the hose.
e) On
all hose 0.5 inch O.D. and larger used in ammonia service and subject to
container pressure, there shall be etched, cast or impressed at 5 ft. intervals
on the outer hose cover the following information:
Anhydrous Ammonia
XXX psig (Maximum
Working Pressure)
Manufacturer’s Name
or Trademark
Year of Manufacture
f) Hose
in service shall be requalified periodically in accordance with requirements
specified in CGA P-7.
g) Hoses
used for transferring material (both liquid and vapor) to and from nurse tanks
shall be restricted to a 30 feet maximum length and shall be secured when not
in use to prevent undue damage to hose.
(Source: Amended at 40 Ill.
Reg. 8704, effective July 1, 2016)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.55 SAFETY RELIEF DEVICES
Section 215.55 Safety Relief
Devices
a) Every
container used in systems covered by Sections 215.85, 215.110, and 215.115
without permanent supply piping to another source of excess pressure shall be
protected from excess pressure by one or more pressure relief valves of the
spring loaded type conforming with applicable requirements of ASME UG-125(c)(3),
UL-132 or other equivalent pressure relief valve standard.
b) Pressure
relief valves shall be in direct communication with the vapor space of the
container. All pressure relief discharge openings shall have suitable rain
caps that will allow free discharge of the vapor and prevent the entrance of
water. Provision shall be made for draining condensate that may accumulate.
c) The
discharge from pressure relief valves shall be vented away from the container,
upward and unobstructed to the atmosphere.
d) Container
relief device pressure shall be set to discharge at no more than 125% maximum
allowable working pressure for containers built by the 1949 ASME Code Sections
U-68 and U-69, and no more than 100% for those built by all subsequent ASME
Codes. Set pressure tolerance is +10% to 0% for non-refrigerated containers.
e) Pressure
relief valves used on containers covered by Sections 215.85, 215.110 and
215.115 shall be constructed to discharge at not less than the rates required
in Appendix B before the pressure is in excess of 121% of the maximum allowable
working pressure of the container. Relief protection for any other reason
shall use ASME UG-125 through UG-136.
f) Pressure
relief valves shall be so arranged that the possibility of tampering will be
minimized. If the pressure setting adjustment is external, the relief valves
shall be provided with means for sealing the adjustment.
g) Shutoff
valves shall not be installed between the pressure relief valves and the
containers or systems covered by Sections 215.85, 215.110 and 215.115.
h) Relief
valves shall be installed in a manifold that has a required rate of discharge
and so installed to allow either of the pressure relief valves to be closed off
but does not allow both pressure relief valves to be closed off at the same
time, or other suitable device so that they can be replaced while the container
remains pressurized. Containers designed with internal pressure relief systems
are exempt from this requirement.
i) Each
pressure relief valve used with systems covered by Sections 215.85, 215.110 and
215.115 shall be plainly and permanently marked as follows:
1) With
the letters "AA" or the symbol "NH3";
2) The
pressure in psig at which the valve is set to start-to-discharge;
3) The
rate of discharge of the valve in cubic feet per minute of air at 60°F and
atmospheric pressure;
4) Year
of manufacture; and
5) The
manufacturer’s name and catalog number.
j) Piping
or connections on either the upstream or downstream side shall not restrict the
flow capacity of the relief valve.
k) The
manufacturer or supplier of a pressure relief valve manifold shall publish
complete data showing the flow rating through the combined assembly of the
manifold with pressure relief valves installed. The manifold flow rating shall
be determined by testing the manifold with all but one valve discharging. If
one or more openings have restrictions not present in the remaining openings,
the restricted opening or openings, or those having the lowest flow, shall be
used to establish the flow rate marked on the manifold nameplate. The marking
shall be similar to that required in Section 215.55 for individual valves.
l) A
hydrostatic relief valve, venting into the atmosphere at a safe location, shall
be installed in each section of piping (including hose) in which liquid can be
isolated between shutoff valves to relieve pressure that could develop from the
trapped liquid. If an equivalent pressure relieving device is used, the maximum
accumulative pressure possible within the system shall not exceed the limits of
the system.
m) The
discharge opening from any pressure relief valve shall not terminate inside any
building or below the highest roof line of the building.
n) A
pressure relief device shall be subject to a systematic, periodic, visual
external inspection at least annually to determine that it:
1) Meets
the applicable requirements specified in this Section;
2) Is
free of evidence of tampering, damage, corrosion or foreign matter that might
prevent proper operation;
3) Is
free of leakage when subject to pressures below the minimum allowable
start-to-discharge setting;
4) Has a
properly installed rain cap or other device to avoid entry of moisture or other
matter into the relief valve outlet; and
5) Has
an open weep hole to permit moisture to escape.
o) Any
deficiency as may be found in subsection (n) shall require immediate corrective
action, replacement or repair of the pressure relief device as may be
appropriate.
p) No
container pressure relief device shall be used over 5 years past the
manufactured date. Records shall be maintained that identify each container
and indicate the date of installation for the pressure relief devices. If no
date is specified, a pressure relief valve shall be replaced no later than five
years following the date of its manufacture or last repair unless it has first
been disassembled, inspected, repaired and tested by the manufacturer, or by a
qualified repair organization, in a manner such that the valve's condition and
performance is certified as being equivalent to the standards for the original
valve. The data regarding repairs or reassembly shall be indicated by stamping
the body or attaching a tag pertaining to the valve with the month and year to
replace or recertify. All facilities shall be in compliance with this subsection
no later than December 31, 2020.
(Source: Amended at 40 Ill.
Reg. 8704, effective July 1, 2016)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.60 FILLING DENSITIES
Section 215.60 Filling
Densities
a) Filling
density is limited to 85% capacity by volume at 60°F.
b) The
filling densities for non-refrigerated containers shall not exceed the
following:
1) Uninsulated
aboveground 56%;
2) Insulated
aboveground 57%.
c) US Department
of Transportation containers shall be filled in accordance with49 CFR 173.315(m)(5).
d) If
containers are to be filled according to liquid level by any gauging method
other than a fixed length dip tube gauge, each container shall have a
thermometer well and thermometer so that the internal liquid temperature can be
easily determined and the amount of liquid and vapor in the container corrected
to a 60°F basis.
(Source: Amended at 40 Ill.
Reg. 8704, effective July 1, 2016)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.65 TRANSFER OF LIQUIDS
Section 215.65 Transfer of
Liquids
a) If it
is found necessary to dispose of anhydrous ammonia, it shall be discharged into
a vessel containing water sufficient to absorb it. Sufficient water shall be
at least ten parts of water per one part anhydrous ammonia. The anhydrous
ammonia shall be injected into the water as near the bottom of the vessel as
practical. Provision must be made to prevent bleeding of transport and
railroad tank car liquid lines or hoses into the atmosphere when disconnecting.
This shall be done through the use of a wet hose with a shutoff valve at each
end of the hose, by bleeding into water at no greater rate than one gallon of
anhydrous ammonia to 10 gallons of ammonia-free water to prevent discharge of
fumes into the atmosphere, or with a recovery system.
b) A certified
competent attendant shall supervise the transfer of liquids from the time the
connections are first made until the railroad tank car is finally disconnected
or the transport truck is completely unloaded and finally disconnected. Any
time the site is unattended, the railroad tank car shall not be connected to
the unloading riser. During the transfer operations of the transport, chock
blocks shall be so placed as to prevent rolling of the vehicle.
c) Containers
shall be filled or used only upon authorization of owners.
d) Containers
shall be gauged and charged only in the open air or in a building especially
provided for that purpose.
e) Pumps
used for transferring anhydrous ammonia shall be recommended for anhydrous
ammonia service by the manufacturer or documented for such service by the
owner/operator using recognized and accepted good engineering methods.
1) Liquid
pumps may be piston, rotary, centrifugal or regenerative type for 250 psig
working pressure.
2) Positive
displacement pumps shall be equipped with a pressure actuated by-pass valve on
the discharge side of the pump. This valve shall operate to limit the pressure
developed by the pump to the maximum for which the pump is rated. Piping or
tubing sized to carry the full capacity of the pump at the actuation pressure
of this valve shall connect the discharge of this valve with the container from
which ammonia is being pumped. If this line is capable of being closed off by
a valve, an additional by-pass device shall be incorporated in the pump to
by-pass back to the suction port. The pressure actuated by-pass valve and the
return piping or tubing shall be installed in accordance with the pump
manufacturer's recommendations or documented for such service by the
owner/operator using recognized and generally accepted good engineering
methods.
3) A
pressure gauge graduated from at least 0 to 400 psig shall be installed before
the relief valve line on the discharge side of the pump.
4) Centrifugal
or regenerative pumps do not require a bypass valve, but the installation shall
incorporate a line from the discharge side of the pump to the vapor space of
the supplying tank and a shutoff valve shall be installed in this line.
f) Plant
piping shall contain shutoff valves located as close as practical to the pump
connections.
g) Compressors
used for transferring or refrigerating ammonia shall be recommended for ammonia
service by the manufacturer or documented for that service by the
owner/operator using recognized and generally accepted good engineering
methods.
1) Compressors,
except those used for refrigeration, shall be designed for at least 250 psig
working pressure. Crank cases of compressors not designed to withstand system
pressure shall be protected with a suitable pressure relief valve.
2) Plant
piping shall contain shutoff valves located as close as practical to compressor
connections.
3) A
relief valve large enough to discharge the full capacity of the compressor
shall be connected to the discharge before any shutoff valve. The discharging
pressure of this valve shall not exceed 300 psig and shall be installed so that
it will be vented in a safe location if discharged.
4) Compressors,
except those used in refrigeration, shall have pressure gauges graduated from
0-400 psig at suction and discharge.
5) Adequate
means, such as a drainable liquid trap, shall be provided on the compressor
suction to minimize the entry of the liquid into the compressor.
h) Piping
shall be designed not to restrict flow rates to the extent that protective
devices will not function.
i) Dedicated
lines for loading and separate dedicated lines for unloading are recommended. Minimum
protection shall be provided as follows:
1) Loading
systems shall be protected by properly rated excess flow valves or approved
systems to prevent the emptying of the storage containers in the event of
severance of the hose or swivel type piping.
2) The
liquid unloading line shall be protected by a back check valve located within 5
lineal feet of pipe from the bulkhead.
3) The
minimum protection for all bypass lines shall consist of an excess flow valve
and a manual shutoff valve. The bypass shall be located at the highest
elevation of the storage tank.
4) System
piping shall be designed to prevent the introduction of debris that could
impede the action of valves and other components of the piping system. All
systems in operation on or before July 1, 2016 shall be in compliance no later
than December 1, 2017. Any piping system installed after July 1, 2016 shall
comply prior to initiation of any operations.
j) Transport
trucks shall not be utilized for bulk storage of anhydrous ammonia. It must be
transferred into permanent storage of a capacity equal to or greater than the
transport truck.
k) Railway
tank cars must be transferred into permanent storage of a capacity equal to 50%
of the railway tank car.
l) All
storage tank system liquid and vapor valves must be closed and locked during
the time the plant is unattended. Either hose end lock boxes or locking caps
or chains may be used on the risers. In lieu of locking the valves, a security
fence with two gates on opposite sides shall be installed and kept locked
during the time the plant is unattended.
m) The
transfer of anhydrous ammonia from a tank car or transport to any other unit
for the purpose of converting anhydrous ammonia to aqueous ammonia shall only
be done upon a railway spur owned or leased to the operator of the transferring
facility where the railway tank car can be retained for an indefinite period
and where an aqueous converter is installed at a site. The transfer must be
done in one continuous operation. The requirements of Section 215.30 must be
met before the site and facility will be approved by the Department. Approved
anhydrous ammonia installations designed for converting aqueous ammonia must
have sufficient permanent storage to permit continuous and uninterrupted
unloading from railway tank cars or trucks.
n) Provision
must be made to prevent bleeding of transport and rail car liquid lines or
hoses into the atmosphere when disconnecting. This shall be done through the
use of a wet hose with a shutoff valve at each end of the hose, by bleeding
into water at no greater rate than one gallon of anhydrous ammonia to 10
gallons of ammonia-free water to prevent discharge of fumes into the
atmosphere, or with a recovery system.
o) A
certified statement shall be filed on forms furnished by the Department stating
that all the requirements of this Section, safety equipment and requirements of
this Part have been met. This statement must be filed with the Department
before final approval of the facility will be given by the Department. No
operation shall begin until final approval has been issued.
p) The
filling of mobile containers with a capacity of 3000 gallons or less with
anhydrous ammonia is permissible only at a permanent storage facility approved
by the Department for this purpose. Anhydrous ammonia may be transferred from
a cargo tank motor vehicle with a maximum capacity of 6000 gallons into
containers of 3000 gallons capacity or less mounted on farm vehicles or
containers of 6000 gallons mounted on motor-driven applicators. This transfer
operation is limited to rural areas and only on the premises of the consignee.
This transfer operation must meet all safety requirements of Section 215.20.
Department approved anhydrous ammonia meters or on board scales shall be
employed for this operation. Meters or on board scales shall conform with the
Weights and Measures Act [225 ILCS 470] and 8 Ill. Adm. Code 600. The selling
price quotation, actual billing, and reporting to the Department shall be done
in pounds or tons.
q) All
stationary storage installations with systems for filling nurse tanks or cargo
vessels with container capacity of 6000 water gallons or less shall have all
vapor and liquid risers protected against any break resulting from a
pull-away. Each vapor and liquid hose shall be protected with an individually
properly rated excess flow valve, a manual control valve, and a break-away or
shear fitting designed to conform with good engineering practices.
r) Meters
used for the measurement of liquid anhydrous ammonia shall be recommended for
ammonia service by the manufacturer and approved by the Department. When dual
purpose meters are used and when changing from LPG to anhydrous ammonia or vice
versa, it is necessary to adjust the coefficient of the expansion scale to the
proper setting for the product being metered. This adjustment will require the
removal of the Illinois Weights and Measures Seal. Section 42 of the Weights
and Measures Act requires that the person who breaks such seal be registered
pursuant to that Act.
s) Liquid
meters shall be designed for a minimum working pressure of 250 psig.
t) The
metering system shall incorporate devices that will prevent the inadvertent
measurement of vapor.
u) Transferring
of anhydrous ammonia from a DOT cargo tank motor vehicle must comply with Transportation
Regulations (see Section 215.16).
v) Bulkheads
shall provide protection during unloading events and shall be accomplished with
the following good engineering practices:
1) All
valves shall be protected from any possible pull-away incidents while connected
between the mobile container and the transfer station in such a manner that any
break resulting from a pull-away will occur on the hose or swivel-type piping
side of the connection while retaining intact the valves and piping on the
plant side of the connection;
2) Installation
of reinforced concrete and structural steel bulkheads or equivalent anchorage,
strong enough not to break and sufficiently massive not to be uprooted by the
motor vehicle;
3) A
manual shutoff valve shall be installed on the liquid and vapor line and
located at the bulkhead;
4) The
use of approved breakaway devices, specifically designed for this purpose;
5) Bulkhead
protection shall not be attached to the container piers; and
6) At
least one caution sign at the bulk heads shall be permanently displayed instructing
the cargo tank driver to chock the cargo tanks wheels prior to loading or
unloading. The signs shall be of metal or other comparable material, at least
8½ inches high by 11 inches wide, and shall state:
CAUTION
DRIVER
MUST CHOCK WHEELS
The signs shall have a yellow
background and the letters shall be at least 1½ inches in height.
(Source: Amended at 40 Ill.
Reg. 8704, effective July 1, 2016)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.70 LIQUID LEVEL GAUGING DEVICES
Section 215.70 Liquid Level
Gauging Devices
a) Each
container, except those filled by weight, shall be equipped with an approved
liquid level gauging device.
b) Each
container or system covered in Sections 215.85, 215.110, and 215.115 shall be fitted
with a liquid level gauge indicating the maximum level to which the container
may be filled with liquid anhydrous ammonia at temperatures between 20°F and
100°F, except on containers provided with fixed maximum level indicators, such
as fixed length dip tubes or containers that are filled by weight. Marks shall
be in increments of not more than 20°F. See Section 215.60 regarding the requirement
for thermometer well and thermometer.
c) Gauging
devices that require bleeding of the product to the atmosphere, such as the
rotary tube, fixed tube, and slip tube devices, shall be designed so that the
maximum opening of the bleed valve is not larger than No. 54 (0.055 in.) drill
size unless provided with an excess flow valve. (This requirement does not apply
to farm vehicles used for the application of ammonia as covered in Section
215.115.)
d) Gauging
devices shall have a design pressure equal to or greater than the design
pressure of the container on which they are installed.
e) Fixed
maximum liquid level gauges shall be designed and installed to indicate a
volumetric level not to exceed 85% of the container’s water capacity.
Note: This does
not apply to refrigerated storage.
f) Gauge
glasses of the columnar type shall be restricted to stationary non-refrigerated
storage installations. They shall be equipped with shutoff valves having
metallic hand wheels, excess flow valves, and extra heavy glass adequately
protected with a metal housing applied by the gauge manufacturer. They shall
be shielded against the direct rays of the sun.
(Source: Amended at 27 Ill.
Reg. 9922, effective July 1, 2003)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.75 PAINTING OF CONTAINERS
Section 215.75 Painting of
Containers
All uninsulated containers shall be painted white or a light
reflecting color.
(Source: Amended at 27 Ill.
Reg. 9922, effective July 1, 2003)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.80 ELECTRICAL EQUIPMENT AND WIRING
Section 215.80 Electrical
Equipment and Wiring
a) Electrical
equipment and wiring for use in ammonia installations shall be general purpose
or weather resistant as appropriate.
b) Where
concentrations of ammonia in air in excess of 16% by volume are likely to be
encountered, electrical equipment and wiring shall be installed to comply with
the requirements specified for use in hazardous locations, Class I, Group D, of
ANSI/NFPA 70, National Electrical Code, Articles 500 and 501.
(Source: Amended at 27 Ill.
Reg. 9922, effective July 1, 2003)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.85 SYSTEMS UTILIZING STATIONARY, PIER-MOUNTED OR SKID-MOUNTED ABOVEGROUND NON-REFRIGERATED STORAGE
Section 215.85 Systems
Utilizing Stationary, Pier-Mounted or Skid-Mounted Aboveground Non-Refrigerated
Storage
a) This Section
applies to stationary, pier-mounted, skid-mounted, aboveground non-refrigerated
storage installations using containers other than those constructed in
accordance with DOT specifications. Section 215.25 applies to this Section
unless otherwise noted. Underground storage tanks are prohibited.
b) The
minimum design pressure for non-refrigerated containers shall be 250 psig.
U-68 and U-69 ASME Code containers with a design pressure of 200 psig are
acceptable for reinstallation if re-certified to 250 psig in accordance with .
CGA G-2, 1 Basic Rules 5.1.
c) All
vapor and liquid connections, except for pressure relief valves and those
specifically exempted in Section 215.40, shall be equipped with approved excess
flow valves (back-pressure check valves are acceptable for filling connections)
or, may be fitted with approved quick-closing internal valves that, except
during operating periods, shall remain closed.
d) Each
storage container shall be provided with a pressure gauge graduated from 0 psig
to 400 psig. Gauges shall be designated for use in ammonia service.
e) All containers shall be
equipped with a suitable vapor equalizing connection.
f) All containers shall be
equipped with a fixed maximum liquid level gauge.
g) Every
container shall be provided with one or more pressure relief valves of
spring-loaded or equivalent type that shall comply with the following
specifications:
1) Relief
valves shall be installed in a manifold or other suitable device so that they
can be replaced while the container remains pressurized. Internal relief
valves are exempt from this requirement.
2) The
discharge from pressure relief valves shall be vented away from the container,
upward and unobstructed to the open air to an area such that persons, property
and the environment will not be harmed. Vent pipes shall not be restrictive or
smaller in size than the pressure relief valve outlet connection. All pressure
relief valves shall have suitable rain caps that will allow free discharge of
the vapor and prevent the entrance of water. Suitable provision shall be made
for draining condensate that may accumulate.
3) If
desired, vent pipes from two or more pressure relief devices located on the
same unit, or similar lines from one or more different units, may be run into a
common header, provided the cross-sectional area of the header is at least
equal to the sum of the cross-sectional areas of the individual vent pipes.
h) Internal
relief valves shall not be used on any tank manufactured after July 1, 2003.
i) Containers
shall be provided with substantial reinforced concrete footings and foundations
or structural steel supports mounted on reinforced concrete foundations. In
either case, the reinforced concrete foundations or footings shall extend below
the established frost line and shall be of sufficient width and thickness to
support the total weight of the containers and contents adequately. Where
required by local codes, seismic loads shall be considered in the design of the
footings and foundations. The foundation shall maintain the lowest point of
the tank not less than 36 inches above the ground. Floating type foundations
shall also be acceptable providing the foundations are designed to adequately
support tank, contents, and piping. (See Section 215.45.) Skid-mounted units
shall include all piping and pumps or compressors as one unit. If the design
of the a unit precludes a minimum of 24 inches ground-to-tank clearance,
bottom-side inlet, outlet valves and piping are prohibited. Skid-mounted
anhydrous ammonia storage tanks must be installed on permanent concrete
footings or adequate floating reinforced concrete slabs.
j) Horizontal
aboveground containers shall be mounted on foundations in such a manner as to
permit expansion and contraction. Every container shall be supported so as to
prevent the concentration of excessive loads. If supports of the saddle type
are employed, the bearing afforded by the saddles shall extend over at least
one-third of the circumference of the shell. Suitable means for preventing
corrosion shall be provided on that portion of the container in contact with
the foundations or saddles.
k) Secure
anchorage or adequate pier height shall be provided against container flotation
wherever sufficiently high flood water might occur.
l) All
anhydrous ammonia storage locations shall have a permanent working platform
installed at each nurse tank or applicator loading location. The working
platform shall be designed to allow for connecting and disconnecting of
transfer hoses without standing on equipment being loaded. This Section does
not apply to nurse tanks or applicators with a working surface designed for
loading purposes.
m) All
on-site structures constructed after July 1, 2016, shall be a minimum of 15
feet in all directions from the aforementioned storage tanks.
n) The
horizontal distance between aboveground containers of over 3000 gallon capacity
shall be at least 5 feet.
o) Each
container or group of containers shall be marked on at least two sides that are
visible with the words ANHYDROUS AMMONIA or CAUTION – AMMONIA in sharply
contrasting colors with letters not less than 4.0 inches high. Two diamond
type, non-flammable gas, UN 1005, USDOT placards may be displayed with letters
not less than 4.0 inches high.
p) Containers
and appurtenances shall be located or protected by suitable barriers so as to
avoid damage by trucks or other vehicles. Main container shutoff valves shall
be kept closed and locked when the installation is unattended.
q) Storage
containers need not be electrically grounded. When an electrical system
exists, such as for lights or pump motors, the electrical system shall be
installed and grounded in a manner as required by the National Electrical Code
or local ordinance.
r) A
sign with letters of a minimum height of two inches giving the name and
telephone number, including area code, of owner, manager or agent of the
anhydrous ammonia storage location shall appear at the site entrances to the
property or apart from the storage tanks.
s) Railroad tank cars shall not be utilized for permanent
anhydrous ammonia storage. Railroad tank cars that are currently in use for
ammonia storage shall not be reinstalled for ammonia use once the container has
been removed from the original saddle. All railroad tank cars used for
permanent storage shall be removed from service pursuant to Section 215.10(c).
(Source: Amended at 40 Ill.
Reg. 8704, effective July 1, 2016)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.90 REFRIGERATED STORAGE
Section 215.90 Refrigerated
Storage
a) This Section
applies specifically to systems using tanks for storage of anhydrous ammonia
under refrigerated conditions. Section 215.25 applies to this Section unless
otherwise stated.
b) Tanks
may be designed for any storage pressure desired as determined by economical
design of the refrigerated system.
c) The
design temperature shall be the minimum temperature to which the container will
be refrigerated and shall be so designated.
d) Containers
with a design pressure exceeding 15 psig shall be constructed in accordance
with Section 215.25 and the material shall be selected from those listed in API
Standard 620, Design and Construction of Large, Welded, Low-Pressure Storage
Tanks, Tables 2.02, R.2.2, R.2.3, or R.2.4.
e) Tanks
with a design pressure of 15 psig or less shall be constructed in accordance
with the general requirements of API Standard 620, including Appendix R.
f) When
austenitic stainless steels or nonferrous metals are used, the ASME Code shall
be used as a guide in selection of materials for use at the design temperature.
g) Tanks
shall be supported on suitable noncombustible foundations designed to
accommodate the type of tank being used.
h) Adequate
protection against flotation or other water damage shall be provided wherever
high flood water might occur.
i) Tanks
storing product at less than 32°F shall be supported in such a way, or heat
shall be supplied, to prevent the effects of freezing and subsequent frost
heaving of the soil.
j) The
area surrounding a refrigerated tank, or group of such tanks, shall be provided
with drainage, diked, or provided with other secondary containment systems to
prevent accidental discharge of liquid from spreading to uncontrolled areas.
k) When
drainage is employed, a slope of not less than 1% shall be provided. The
drainage system shall terminate in an impounding basin having a capacity as
large as the largest tank served.
l) Provision
shall be made for the drainage of rain water from the dike or impounding area.
Such drainage shall be provided with a positive means to stop the flow.
m) Where
a dike is employed, the capacity of the diked enclosure shall be 110% of the
capacity of the largest tank served. When computing the volume of the dike,
allowance shall be made for the volume displaced by all other containers in the
diked area.
n) The
walls of a diked enclosure or the wall of an impounding basin used in a
drainage system shall be of earth, steel, concrete, or other suitable material
designed to be liquid tight and to withstand the hydrostatic pressure and
temperature. Earth walls shall have a flat top at least 2 feet wide. The
slope shall be stable and consistent with the angle of repose of the earth
used.
o) The
ground in an impounding basin or with a diked enclosure should be graded so that
small spills or the early part of a large spill will accumulate at one side or
corner, thereby contacting only a relatively small area of ground and exposing
a relatively small area for heat gain. Shallow channels in the ground surface
or low curbs of earth can help guide the liquid to these low areas without
contacting a large ground area.
p) Each
refrigerated container shall be marked with a nameplate on the outer covering
in an accessible place as specified in the following:
1) With
the name and address of the builder and the date of fabrication;
2) With
the maximum volume or weight of the product, whichever is most meaningful to
the user;
3) With
the design pressure;
4) With
the minimum temperatures in degrees Fahrenheit (°F) or degrees Celsius (°C) for
which the container was designed;
5) With
the maximum allowable water level to which the container may be filled for the
test purposes;
6) With
the density of the product in pounds per cubic foot or kilograms per cubic
meter for which the container was designed; and
7) With
the maximum level to which the container may be filled with liquid anhydrous
ammonia.
q) Each
refrigerated container shall be marked on two directly opposite sides at near
eye level with the words ANHYDROUS AMMONIA or CAUTION – AMMONIA in sharply
contrasting colors with letters not less than 4.0 inches high.
r) Each
refrigerated container shall be conspicuously marked with a hazard warning
label complying with 29 CFR 1910.1200.
s) Shutoff valves shall be:
1) Provided
for all connections except those with a No. 54 (0.055 inches) drill size
restriction, plugs, pressure relief valves, and thermometer wells; and
2) Located
as close to the tank as practical.
t) A
check valve shall be installed on the tank liquid fill connection if it is
located below the maximum liquid level. A remotely operated shutoff valve shall
be installed on other connections located below the maximum liquid level. See
Section 215.65.
u) Each
refrigerated container shall be equipped with an approved liquid level gauging
device and high liquid level alarm.
v) The
tank shall be provided with a system of one or more pressure relief valves that
can limit the tank pressure below 115% (110% if only one pressure relief valve
is used) of the design pressure during operational emergency conditions other
than fire and below 121% of the design pressure during operational emergency
conditions that include fire. One of the pressure relief valves shall be set
to start to discharge at a pressure not in excess of the design pressure of the
tank, and all other pressure relief valves needed to limit the tank pressure
below 115% (110% if only one pressure relief valve is used) of the design
pressure during operational emergency conditions other than fire shall be set
to discharge at a pressure not in excess of 105% of the design pressure. All
additional pressure relief valves needed to limit the tank pressure below 121%
of the design pressure during operational emergency conditions, including fire,
shall be set to start to discharge at a pressure not in excess of 110% of the
design pressure.
w) The
pressure relief valve set to discharge below 105% of the design pressure of the
tank shall have a total relieving capacity in excess of the relieving capacity
required to handle operating emergency conditions listed in subsection (x).
The total relieving capacity of all the pressure relief valves in the system
shall be the larger requirement of subsection (x) or (y).
x) Possible
refrigeration system upsets are cooling water failure; power failure;
instrument air or instrument failure; mechanical failure of any equipment;
excessive pumping rates; and changing atmospheric conditions.
y) Use
either of the following formulas for fire exposure. Relief valve sizing for
fire protection may be adjusted to protect against the worst possible fire
exposure.
1) For
valve manufacturers who classify valves on the basis of the weight of the
vapors to be relieved:
■

■
2) For
valve manufacturers who classify valves on the basis of air flow:

3) Where:
|
W
|
=
|
weight of vapors to be relieved in pounds/hour at
relieving conditions
|
|
|
|
|
|
Qa
|
=
|
air flow in cubic feet per minute at standard conditions
60°F and 14.7 psi
|
|
|
|
|
|
F
|
=
|
fireproofing credit. Use F = 1.0 except when an approved
fireproofing material of recommended thickness is used, in which case use F =
0.2
|
|
|
|
|
|
A
|
=
|
total surface area in square feet up to 25 feet above
grade or to the equator of a sphere, whichever is greater
|
|
|
|
|
|
Z
|
=
|
compressibility factor of ammonia at relieving condition
(if not known, use Z = 1.0)
|
|
|
|
|
|
T
|
=
|
temperature in degrees R (460 + temperature in °F of gas
at relieving conditions)
|
|
|
|
|
|
M
|
=
|
molecular weight = 17 for ammonia
|
|
|
|
|
|
L
|
=
|
latent heat of ammonia at relieving conditions in Btu per
pound
|
|
|
|
|
|
C
|
=
|
constant based on relation of specific heats (C may be
obtained from the following table)
|
(If K is not known, use C =
315)
|
K
|
C
|
K
|
C
|
K
|
C
|
|
1.00
|
315
|
1.26
|
343
|
1.52
|
366
|
|
1.02
|
318
|
1.28
|
345
|
1.54
|
368
|
|
1.04
|
320
|
1.30
|
347
|
1.56
|
369
|
|
1.06
|
322
|
1.32
|
349
|
1.58
|
371
|
|
1.08
|
324
|
1.34
|
351
|
1.60
|
372
|
|
1.10
|
327
|
1.36
|
352
|
1.62
|
374
|
|
1.12
|
329
|
1.38
|
354
|
1.64
|
376
|
|
1.14
|
331
|
1.40
|
356
|
1.66
|
377
|
|
1.16
|
333
|
1.42
|
358
|
1.68
|
379
|
|
1.18
|
335
|
1.44
|
359
|
1.70
|
380
|
|
1.20
|
337
|
1.46
|
361
|
2.00
|
400
|
|
1.22
|
339
|
1.48
|
363
|
2.20
|
412
|
|
1.24
|
341
|
1.50
|
364
|
|
|
4) Where
|
K
|
=
|
Cp at atmospheric
conditions
|
|
|
Cv
|
|
|
Cp
|
=
|
specific heat of vapor at constant pressure
|
|
Cv
|
=
|
specific heat of vapor at constant volume
|
z) Shutoff
valves of adequate flow capacity may be provided and used to facilitate
inspection and repair of pressure relief valves. When a shutoff valve is
provided, it shall be so arranged that it can be locked or sealed open, and it
shall not be closed except by an authorized person who shall remain stationed
there while the valve remains closed and who shall again lock or seal the valve
open when leaving the station.
aa) Pressure relief valves
shall comply with the following:
1) If
stacks are used they shall be suitably designed to prevent obstruction by rain,
snow, ice, or condensate.
2) The
outlet size shall not be smaller than the nominal size of the pressure relief
valve outlet connection.
bb) Discharge
lines may be used if desired. Multiple pressure relief valves on the same
storage unit may be run into a common discharge header. The discharge line and
header shall be designed to accommodate the maximum flow and a back pressure
not exceeding 10% of the design pressure of the storage container. This back
pressure shall be included to limit total tank pressure below 121% of the
design pressure given in subsection (v). No other container or system shall
exhaust into this discharge line or header. The vent lines shall be installed
to prevent accumulation of liquid in the lines.
cc) The
discharge from pressure relief valves shall be vented away from the container,
upward and unobstructed to the open air to an area such that persons, property,
and the environment will not be harmed. All pressure relief valves shall have
suitable rain caps that will allow free discharge of the vapor and prevent the
entrance of water. Suitable provision shall be made for draining condensate
that may accumulate.
dd) Atmospheric
storage shall be provided with vacuum breakers of adequate capacity to respond
to anticipated rates of liquid withdrawal and to rapid atmospheric changes so
as to avoid damage to the container. Ammonia gas may be used to provide a pad.
ee) Pressure
relief valves used to protect other systems at refrigerated storage
installations shall discharge to the open air unless connected to a control
device as defined in Section 215.55.
ff) Because
emergency venting for a double-wall refrigerated storage tank is complex, no
calculation method is presented here. A thorough analysis of the fire relief
for a double-wall refrigerated storage tank should be conducted.
gg) Refrigerated
storage containers and appurtenances shall comply with the provisions of
Section 215.40.
hh) Containers
of such size as to require a field fabrication shall, when moved and
reinstalled, be reconstructed and re-inspected in complete accordance with the
original requirements under which they were constructed. The containers shall
be subjected to a pressure retest, and if re-rating is necessary, it shall be
done in accordance with the applicable pressure of the original requirements.
ii) The
total refrigeration load shall be computed as the sum of the following:
1) Load
imposed by heat flow into the container caused by the temperature differential
between the ambient temperature and the storage temperature;
2) Load
imposed by heat flow into the tank caused by maximum sun radiation; and
3) Maximum
load imposed by filling the tank with ammonia warmer than the design storage
temperature.
jj) More than one storage
tank may be handled by the same refrigeration system.
kk) A
minimum of two compressors shall be provided, either of which is of sufficient
size to handle the loads listed in subsections (ii)(1) and (ii)(2), except as
provided in subsection (mm). Where more than two compressors are provided,
minimum standby equipment equal to the largest normally operating equipment
shall be installed. Compressors required for subsection (ii)(3) may be used as
standby equipment for compressors required in subsections (ii)(1) and (ii)(2).
ll) Compressors
shall be sized to operate with a suction pressure at least 10% below the
minimum setting of the pressure relief valves on the storage tank and shall
withstand a suction pressure at least equal to 121% of the design pressure of
the tank. Discharge pressure will be governed by condensing conditions.
mm) Where
facilities are provided to safely dispose of vented vapor to an automatic flare
or to a process unit, a single compressor of sufficient size to handle the load
listed in subsections (ii)(1) and (ii)(2) shall be allowed.
nn) Each compressor shall have
its own drive unit.
oo) Any standard drive
consistent with good design may be used.
pp) An
emergency source of power of sufficient capacity to handle the loads listed in subsections
(ii)(1) and (ii)(2) shall be provided unless facilities are provided to safely
dispose of vented vapors while the refrigeration system is not operating.
qq) The
refrigeration system shall be arranged with suitable controls to govern the
compressor operation in accordance with the load as evidenced by the pressure
in the containers.
rr) An
emergency alarm system shall be installed to function in the event the pressure
in the containers rises to the maximum or falls to the minimum allowable
operating pressure.
ss) An
emergency alarm and shutoff shall be located in the condenser system to respond
to excess discharge pressure caused by failure of the cooling medium.
tt) All
automatic controls shall be installed in a manner to preclude operation of
alternate compressors unless the controls will function with the alternate
compressors.
uu) An
entrainment separator of suitable size and design pressure shall be installed
in the compressor suction line. The separator shall be equipped with a drain
and gauging device. A maximum liquid level control with alarm should be
installed.
vv) An oil
separator of suitable size shall be installed in the compressor discharge
line. It shall be designed for at least 250 psig and shall be equipped with a
gauging device and drain valve. A maximum oil level control with alarm should
be installed.
ww) A
separator shall be equipped with a pressure relief valve if the separator can
be isolated with shutoff valves.
xx) The
condenser system may be cooled by air or water or both. The condenser shall be
designed for at least 250 psig. Provision shall be made for purging
noncondensibles either manually or automatically.
yy) The
condenser shall be equipped with a pressure relief valve if the condenser can
be isolated with shutoff valves.
zz) A
condenser effluent receiver shall be provided that is equipped with automatic
level controls and valving designed to discharge the liquid ammonia to storage,
or with a high-pressure liquid drain trap of suitable capacity. The receiver
shall be designed for at least 250 psig operating pressure and be equipped with
the necessary connections, pressure relief valves, and gauging device.
aaa) Refrigerated
containers and pipeline that are insulated shall be covered with a material of
suitable quality and thickness for the temperatures encountered. Insulation
shall be suitably supported and protected against the weather. Weatherproofing
and insulation shall be of a type that will not support flame propagation and
will not cause corrosion when wet.
bbb) Each
refrigerated storage installation shall have on hand the minimum safety equipment
required in Section 215.20.
ccc) In
addition to the safety equipment requirement in Section 215.20, each
refrigerated storage installation shall have on hand at least two independently
supplied, positive-pressure SCBAs and at least two approved encapsulating
corrosive chemical suits that are impervious to ammonia. Each shall be
designed to accommodate an SCBA.
ddd) A sign
with letters of a minimum height of two inches giving the name and telephone
number, including area code, of owner, manager or agent of the anhydrous
ammonia storage location shall appear at the site entrances to the property or
apart from the storage tanks.
(Source: Amended at 27 Ill.
Reg. 9922, effective July 1, 2003)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.95 TANK CAR OPERATIONS
Section 215.95 Tank Car
Operations
a) Anhydrous
ammonia tank cars shall be transferred only at permanent storage locations into
permanent storage containers.
b) Transfer operations
shall be performed by a certified competent attendant.
c) Rail track at tank car
transfer positions shall be essentially level.
d) Brakes
shall be set and the wheels blocked in both directions on all tank cars being
loaded or unloaded.
e) Caution
signs shall be so placed on the track or car to give necessary warning to
persons approaching the car from the open end or ends of the siding. The signs
must be of metal or other comparable material at least 12 inches high by 15
inches wide in size, and bear the words, STOP – TANK CAR CONNECTED or STOP –
MEN AT WORK, the word STOP being in letters at least 4 inches high. Other
words should be in letters at least 2 inches high. The letters must be white
on blue background. A car so protected must not be coupled or moved. The
signs must remain in place until the tank car valves have been closed and the
transfer lines have been disconnected.
f) A
standard derail must be properly set and secured in the derailing position
between the railroad tank car being loaded or unloaded and other cars being
moved on the same track.
g) After
a transfer, all valves shall be closed and transfer lines disconnected. Caps
or plugs on railroad tank car sample valves, liquid valves, vapor valves, and
gauging device valves shall be replaced and made wrench tight. Slip tube
gauging devices shall be secured and gauge housings screwed in place.
Protective housing covers must be secured and pinned and proper seals put in
place when required. Leaks from any source on a tank car shall be stopped
before a car may be released to the carrier.
(Source: Amended at 40 Ill.
Reg. 8704, effective July 1, 2016)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.100 SYSTEMS UTILIZING STATIONARY, PIER-MOUNTED OR SKID-MOUNTED ABOVEGROUND OR UNDERGROUND NON-REFRIGERATED STORAGE (REPEALED)
Section 215.100 Systems
Utilizing Stationary, Pier-Mounted or Skid-Mounted Aboveground or Underground
Non-Refrigerated Storage (Repealed)
(Source: Repealed at 27 Ill.
Reg. 18536, effective November 25, 2003)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.105 SYSTEMS MOUNTED ON FARM WAGONS (IMPLEMENTS OF HUSBANDRY) FOR THE TRANSPORTATION OF ANHYDROUS AMMONIA (REPEALED)
Section 215.105 Systems
Mounted on Farm Wagons (Implements of Husbandry) for the Transportation of
Anhydrous Ammonia (Repealed)
(Source: Repealed at 27 Ill.
Reg. 18536, effective November 25, 2003)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.110 SYSTEMS MOUNTED ON IMPLEMENTS OF HUSBANDRY FOR THE TRANSPORTATION OF ANHYDROUS AMMONIA
Section 215.110 Systems
Mounted on Implements of Husbandry for the Transportation of Anhydrous Ammonia
All of Section 215.25 shall
apply to this Section unless otherwise stated.
a) This Section
applies to containers of 3000 gallons water capacity or less and related
equipment mounted on nurse tanks that are used for the transportation of
ammonia.
1) Any
nurse tank that does not have a legible data plate and has not been recertified
in conformance with Transportation Regulations (see Section 215.16) shall be
removed from service.
2) Any
container or combination of containers on a
single running gear, greater than 3000 gallons, that are used for the
transportation of anhydrous ammonia and to supply the application device shall
be prohibited. This shall exclude cargo tanks used for transportation only.
b) Containers
shall be constructed in accordance with Section 215.25. The shell or head
thickness of any container shall not be less than 3/16 of
an inch. All containers over 500 gallons capacity should be equipped with
semi-rigid baffle plates.
c) A
suitable "stop" or "stops" shall be mounted on the farm
wagon or on the container in such a way that the container shall not be
dislodged from its mounting due to the farm wagon coming to a sudden stop.
Back slippage shall also be prevented by proper methods.
d) A
suitable "hold-down" device shall be provided that will anchor the
container to the farm wagon at one or more places on each side of the
container.
e) When multiple
containers are mounted on a running gear, the weight shall be distributed appropriately
over the axles. Multiple containers mounted on the same running gear must be
of the same capacity. All manual shutoff valves shall be located behind the
steel bulkhead or permanently affixed in a secure point to provide equivalent
protection of the piping from that point to the front of the tank.
f) When
the cradle and the container are not welded together, suitable material shall
be used between them to reduce abrasion.
g) All containers shall be
equipped with a fixed maximum liquid level gauge.
h) All
containers shall be equipped with a pressure gauge having a dial graduated from
0 psi to 400 psi.
i) The
filling connection of each container shall comply with the requirements of
Section 215.40(j).
j) All
containers shall be equipped with an approved vapor-equalizing valve unless
equipped for spray loading.
k) All
vapor and liquid connections, except pressure relief valves and those
specifically exempt in Section 215.40(e) and (f) shall be equipped with
approved excess flow valves or may be fitted with quick-closing internal valves
that shall remain closed except during operating periods. Every tank
withdrawal valve shall be protected by an excess flow valve matched to the
designed flow rate. Flow capacity of the excess flow valve shall not exceed 45
GPM for 1¼" tank connections and 60 GPM for 1½" tank connections. When
using an open yoke type excess flow withdrawal valve in a tank opening, the
opening shall not be reduced with bushings to accommodate the withdrawal valve.
Each valve shall be tested through the Nurse Tank Inspection Program (NTIP) or be
removed and inspected at an interval not to exceed 5 years. Records of the
maintenance and inspections shall be kept at the facility for review. All
valves shall be in compliance no later than December 31, 2020. Nurse tanks not
meeting compliance shall be removed from service.
l) Fittings
shall be protected from physical damage by means of a rigid guard designed to
withstand static loading in any direction equal to twice the weight of the
container and lading using a safety factor of 4 based upon the ultimate strength
of the material used. If the guard encloses the pressure relief valve, the
valve shall be properly vented through the guard.
m) If a
liquid withdrawal line is installed in the bottom of a container, the
connections to that line, including hose, shall not be lower than the lowest
horizontal edge of the farm wagon axle. The hose shall be drained and
depressurized prior to the container being moved or towed on a public road.
n) Provision shall be made
to secure both ends of the hose in transit.
o) All containers shall be
painted white or a light reflecting color.
p) All containers shall be
marked as follows:
1) Placard:
Four diamond type, nonflammable gas, UN 1005, USDOT placards shall be
displayed (one on each side and one on each end).
2) Marking:
The words ANHYDROUS AMMONIA shall appear on each side and each end in letters
no less than 2 inches high.
3) Each
container shall be marked with the words INHALATION HAZARD in 2 inch letters on
2 opposing sides.
4) The
words LIQUID or VAPOR shall be placed on or within 12 inches of the appropriate
valve by means of stencil, tag, decal or color coding with a legible legend
ORANGE LIQUID and YELLOW VAPOR on the tank.
5) The
container need not be marked or placarded on one end if that end contains
valves, fittings, regulators or gauges when those appurtenances prevent the
markings and placard from being properly placed and visible.
q) Nurse
tanks operating on public roads shall be marked with a slow-moving vehicle
(SMV) emblem consisting of a fluorescent orange triangle with a red reflective
border. The specifications of the SMV shall be the type recommended by ASAE
S276.5. Nurse tanks operating on public roads are to travel at speeds less
than 25 mph.
r) All nurse
tanks shall be securely attached to the vehicle drawing them by means of
drawbars supplemented by suitable hitch pins with clips and safety chains permanently
attached to the farm wagon.
s) A nurse
tank shall be constructed so that it will follow substantially in the path of
the towing vehicle and will prevent the towed farm wagon from whipping or
swerving dangerously from side to side.
1) Nurse
tanks require two safety chains with a combined breaking strength of at least
the weight of the laden nurse tank.
2) All
nurse tanks shall be securely attached to the vehicle drawing them by means of
drawbars supplemented by suitable hitch pins and safety chains that meet the
requirements of ASAE S338.2, Safety Chain for Towed Equipment. Reliable
keepers for the hitch pin shall be used to prevent its loss. The hitch pin and
keeper shall be permanently attached to the nurse tank towbar.
t) A nurse
tank shall not be towed or parked in public places such as school yards, malls
or hospital grounds.
u) Each
person operating, repairing appurtenances to, or inspecting a nurse tank shall
wear protective gloves impervious to ammonia and chemical splash goggles. A
full face shield may be worn over the goggles; however, a face shield shall not
be worn as a substitute for a primary eye protection device (goggles).
v) For
first aid purposes each nurse tank shall be equipped with at least 5 gallons of
clean water in a container mounted on top or side of the tank designed to
provide ready access to the water for flushing any area of the body contacted
by ammonia.
w) Prior
to the addition of a chemical additive, its compatibility with system
components shall be verified by the manufacturer of the additive.
x) Storage
of Containers: When a nurse tank containing 10% or more of anhydrous ammonia is
at an unattended approved storage site, the manually controlled valves shall be
plugged or capped or locked or the nurse tank shall be stored inside a locked,
fenced enclosure. Nurse tanks shall be stored no less than 50 feet from the
edge of the adjacent road, 200 feet from place of private or public assembly
and 750 feet from place of institutional occupancy. All pressure and liquid
gauges must be in working order.
y) A
back check valve shall be installed on each inlet of each fitting (including,
but not limited to, tees and crosses) to prevent the back feed of anhydrous
ammonia from an undamaged line to a damaged/severed line. All multiple tank
configurations shall have equally rated liquid withdrawal valves on each tank. An
excess flow valve with the same rated flow as the aforementioned valves shall
be installed at the junction where the lines meet downstream. A shutoff valve
shall be installed downstream of the excess flow valve.
AGENCY NOTE: If tanks are not
plumbed together, they shall be treated as single tanks. Tanks with equally
rated internal valves with remote actuators are exempt from this requirement. Compliance
with these requirements shall be achieved through repairs and modifications on
or before December 31, 2025.
z) Excess
flow valves shall be designed to close automatically at the rated flows of
vapor or liquid as specified by the manufacturer. Excess flow valves shall be
selected based on the piping, including valves, fittings and hoses being protected
by an excess flow valve, and shall have a greater capacity than the rated flow
of the excess flow valve, so the valve will likely close in case of delivery
system failure at any point in the line or fittings. Any installation of a
device that may cause a reduction in pressure to impede the operation of the
excess flow valve is prohibited.
aa) All liquid and vapor service valves shall be protected by a
threaded cap that must be affixed to the valve housing.
(Source: Amended at 44 Ill.
Reg. 18281, effective October 29, 2020)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.115 SYSTEMS MOUNTED ON EQUIPMENT FOR THE APPLICATION OF ANHYDROUS AMMONIA
Section 215.115 Systems
Mounted on Equipment for the Application of Anhydrous Ammonia
a) This Section
applies to systems mounted on farm equipment and used for the field application
of ammonia. Section 215.25 applies to this Section unless otherwise noted.
b) The
shell or head thickness of any container shall not be less than 3/16
of an inch.
c) All
containers shall be securely mounted. Applicators must be secured with hold-down
devices the same way as systems mounted on farm wagons transporting anhydrous
ammonia.
d) Fixed
maximum liquid level gauges shall be used that are designed to indicate when
the container has been filled to 85% of its water capacity. The dip tube of
this gauge shall be installed in such a manner that it cannot be readily
removed.
e) The
filling connection of each container shall comply with the requirements of
Section 215.40(k).
f) An
excess-flow valve is not required in the vapor connection, provided the
controlling orifice is not in excess of 5/16 inch in
diameter and the valve is a hand-operated (attached hand wheel or equivalent)
shutoff valve. To assist in filling applicator tanks, it is permissible to
bleed vapors to the open air, provided the preceding requirements are met.
g) Applicators
shall be filled at least 100 yards from any occupied building not on an approved
site.
h) Metering
devices may be connected directly to the tank withdrawal valve. A union-type
connection is permissible between the tank valve and the metering device.
Remote mounting of metering devices is permissible using hoses that meet
specifications.
i) When
the applicator or nurse tank is trailed and the metering device is remotely
mounted, such as on the tractor tool bar, an automatic break-away, self-closing
coupling device shall be used. The coupling device shall be made from or
coated with a corrosion resistant material. The coupling device shall be
mounted in a manner that will permit the device to swivel freely. A coupling
device shall be maintained. An angle valve shall not be used as a hose end
valve connecting to the coupling device.
j) No
excess-flow valve is required in the liquid withdrawal line provided the
controlling orifice between the contents of the container and the outlet of the
shutoff valve (see Section 215.40(c)) does not exceed 5/16
in diameter.
k) Any
control valve installed between the regulator and the break-away coupling
device shall indicate whether the valve is open or closed.
l) Where
a ball valve is used to control flow to the metering device, the ball shall be
drilled with an opening smaller than No. 54 (0.055 inches) drill size on the downstream
side to prevent trapping ammonia in the ball when in the closed position.
m) Each
person operating, repairing, or inspecting an applicator shall wear protective gloves impervious to ammonia and chemical
splash goggles. A full face shield may be worn over the goggles; however, a
face shield shall not be worn as a substitute for a primary eye protection
device (goggles).
n) Each
applicator tank shall be equipped with the following safety equipment and
features: for first aid purposes, at least 5 gallons of clean water in a
container designed to provide ready access to the water for flushing any area
of the body contacted by ammonia and a legible decal depicting step-by-step
ammonia transfer instructions.
o) Instructions
for connecting and disconnecting the coupling device shall be displayed in a
manner as to be readily visible near the break-away coupling device.
(Source: Amended at 44 Ill.
Reg. 18281, effective October 29, 2020)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.120 EQUIPMENT FOR THE APPLICATION OF ANHYDROUS AMMONIA
Section 215.120 Equipment
for the Application of Anhydrous Ammonia
a) All nurse tank valves shall be closed, the liquid transfer
hose shall be bled, and no liquid transfer hose shall be joined between any
nurse tank unit and any tool bar during transport upon a public right-of-way.
b) The following requirements apply when liquid transfer hoses
are permanently attached to nurse tank units or tool bars:
1) Only the end of the liquid transfer hose, that is attached to
a male acme-threaded fitting of the tool bar breakaway device shall be equipped
with a straight-type hose end valve with a bleeder valve on its coupling side.
2) The hose end valve specified in subsection (b)(1) shall not be
attached to a container fill valve of the same nurse tank unit.
3) A dummy acme adapter or parking plug shall be provided on the
nurse tank or tool bar. The dummy acme adapter or parking plug shall be affixed
into a position that prevents either end of the hose from being kinked or
stowed under undue strain. The hose end valve of the liquid transfer hose shall
be connected to the dummy acme adapter or parking plug at all times, except
when the transfer hose is used for field application or other active transfer
of ammonia through the hose end valve.
c) When nurse tanks are utilized to supply an application device,
some means of break-away protection shall be provided, including, but not
limited to, the following:
1) The nurse tank hose that crosses the
hitching point and attaches to the application device requires installation of
the appropriate equipment to protect against an accidental unhitching event.
Deployment of the equipment designed to achieve this protection shall be
installed and maintained in accordance with the manufacturer's instructions.
2) Multiple breakaway coupling devices
mounted on a tool bar shall not interfere with one another in a turn or an
unhitching event.
3) When nurse tanks are pulled in
tandem, a breakaway coupling device or other means of protection shall be
installed at each point where the hose crosses a hitching point. Deployment of
the equipment designed to achieve this protection shall be installed and
maintained in accordance with the manufacturer's instructions. Compliance with
this subsection (c)(3) shall be achieved on or before December 31, 2020.
d) The manufacturer of a tool bar
refrigeration unit shall provide with each unit documentation of recommended
operation and maintenance procedures for any refrigeration unit manufactured
after July 1, 2016.
1) The
tool bar refrigeration unit shall be installed, maintained and operated in
accordance with the manufacturer's specifications and limitations of use.
2) A
manual shutoff valve shall be installed directly upon the inlet of the heat
exchanger so that the operator may close the shutoff valve to prevent any
backflow of refrigerated ammonia through the delivery line from the heat
exchanger unit while connecting, disconnecting or otherwise servicing the tool
bar breakaway device.
e) Hose and hose connections located on the low-pressure side of
flow control, or pressure-reducing valves on devices discharging to atmospheric
pressure, shall be designed for the maximum low-side working pressure. EVA
hoses for tool bars shall be inspected for leaks and documented prior to each
application season. The hoses shall not exceed the service life specified by
the tubing manufacturer and shall comply with the properly rated operating
pressure specified by the equipment manufacturer.
f) Any application device designed to tow two nurse tanks with a
total static capacity greater than 4000 gallons shall employ the following:
1) The device shall include two separate distribution systems on
the tool bar, one for each nurse tank.
2) The device and/or nurse tanks shall have enhanced protection
systems that include the capability for emergency shutoff with immediate
response. In addition, other systems may be deployed pending approval by the Department.
g) The hose length from the towed implement mechanically secure
point to the break-away coupler on the towing implement shall have sufficient
length to allow break-away couplers to articulate freely but prevent the hose
from contact with the nurse tank tongue. This shall be achieved without
securing the hose mechanically through the use of chains, elastomeric straps,
wire ties or other means, by December 31, 2020. New technologies and methods
that allow for mechanical hose securement that do not affect the coupler
functionality will be accepted, but may later be denied for observed "non-performance".
(Source: Amended at 44 Ill.
Reg. 18281, effective October 29, 2020)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.125 ADMINISTRATIVE HEARINGS
Section 215.125
Administrative Hearings
Decisions of the Department in implementing this Part are
subject to the Illinois Administrative Procedure Act [5 ILCS 100] and the
Department's rules pertaining to administrative hearings (8 Ill. Adm. Code 1).
(Source: Section 215.125
renumbered from Section 215.120 at 40 Ill. Reg. 8704, effective July 1, 2016)
SUBPART B: NITROGEN FERTILIZER SOLUTIONS
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.200 GENERAL
Section 215.200 General
a) Nitrogen fertilizer solutions are divided into subcategories
as follows:
1) Aqua ammonia solution (Ammonium
Hydroxide) is an aqueous solution of anhydrous ammonia generally containing
from 18 to 30 percent of ammonia (NH3) by weight and having a vapor
pressure usually varying from 0 to 10 psig at 104 degrees Fahrenheit (F). Aqua
ammonia may be handled in free-vented nurse and applicator tanks provided the
time between filling and application into the ground is held to a minimum.
Freezing point of a 25 percent aqua ammonia solution is approximately -67
degrees F. while higher percentages will have lower freezing points. Specific
gravity usually ranges from .89 to about .93 depending upon temperature and
concentration.
2) Low pressure nitrogen fertilizer solution is an aqueous
solution of ammonia nitrate and/or urea and/or sodium nitrate and/or other
nitrogen carriers, containing various quantities of free ammonia exceeding 2
percent by weight. Vapor pressure usually ranges from 0 to 30 psig at 104
degrees F. although for direct application the range is usually from 0 to less
than 20 psig. These solutions shall be stored in pressure-vented tanks equipped
with safety pressure relief and vacuum relief valves. Application and nurse
tank equipment may be free vented for some of these solutions provided the time
between filling and application is held to a minimum. Saturation temperature
usually ranges from below -40 degrees F. to +65 degrees F. Specific gravity usually
varies from 0.90 to 1.20.
b) In the interest of safety, personnel storing and handling
nitrogen fertilizer solutions should be knowledgeable in the safe control and
handling of these solutions. The Department conducts a training program in
nitrogen safety procedures.
c) Ammonia vapor has a pungent odor which serves as its own
warning agent. Ammonia vapor is lighter than air. Out-of-doors handling and
adequate ventilation are best means of preventing accumulation. The flammable
limits to free ammonia are from 16 to 25 percent by volume in air. Experience
has shown that ammonia is extremely hard to ignite in spite of these
theoretical limits and is generally considered to be a non-flammable gas.
Ammonium nitrate starts to decompose at temperatures above 410 degrees F.
Welding should not be attempted on any system which has contained nitrogen
fertilizer solutions without proper preparation (see 8 Ill. Adm. Code Section
215.Table D).
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.205 DEFINITIONS
Section 215.205 Definitions
a) The terms defined in 8 Ill. Adm. Code Section 215.15 shall
pertain to the rules in this Subpart. The term "nitrogen fertilizer
solution" should be substituted in lieu of the term "anhydrous
ammonia" where it appears in those definitions.
b) In addition to terms defined in 8 Ill. Adm. Code Section
215.15, the following terms shall apply to this Subpart:
1) "Closed system" refers to a transfer system which
will return displaced vapor to the tank from which the liquid is being
discharged.
2) "Filling volume" is defined as the percent ratio of
the liquid in a container to the volume of the container.
3) "Free vented" as used means the system is
permanently open to the atmosphere. No shutoff or check valve is allowed in
such opening.
4) "Hold-down devices" refers to chains or metal straps
or cables.
5) "Hold to a minimum" means the product should be
loaded in anticipation of sale into the nurse tanks and delivered to the
consumer for use without being stored in nurse tanks waiting for a consumer
order.
6) "Nitrogen fertilizer solutions" refers to compounds
(ammonium nitrate, urea, sodium nitrate, and other nitrogen carriers) formed by
the combination of free ammonia and water with or without other nitrogen
salts. Nitrogen fertilizer solutions includes all liquid containing more than
2% free ammonia and/or having 5 psig. It does not include material containing
over 1% of phosphorous and/or potassium which is used as plant food.
7) "Pressure vented" is a system equipped with a
pressure relief valve or a combination pressure-vacuum relief valve.
8) "Vacuum" refers to ounces per square inch of
pressure below atmospheric pressure.
9) "Vapor pressure," unless otherwise specified, shall
refer to the pressure developed by the solution at temperature specified.
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.210 APPLICATION OF RULES
Section 215.210 Application
of Rules
a) These rules apply to the design, location, construction,
installation and operation of distribution systems utilizing nitrogen
fertilizer solutions or aqua ammonia converters.
b) 8 Ill. Adm. Code Sections 215.215 through 215.260 apply to all
sections unless otherwise specified.
c) 8 Ill. Adm. Code Section 215.265 applies to storage
installations for nitrogen fertilizer solutions.
d) 8 Ill. Adm. Code Section 215.270 applies to systems mounted on
tank trucks, semi-trailers and trailers for transportation of nitrogen
fertilizer solutions.
e) 8 Ill. Adm. Code Section 215.275 applies to systems mounted on
vehicles and implements of husbandry for the transportation of nitrogen
fertilizer solutions.
f) 8 Ill. Adm. Code Section 215.280 applies to systems mounted on
farm vehicles for the application of nitrogen fertilizer solutions.
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.215 REQUIREMENT OF CONSTRUCTION AND ORIGINAL TEST OF CONTAINERS
Section 215.215 Requirement
of Construction and Original Test of Containers
a) Containers shall be constructed of a material suitable for use
with nitrogen fertilizer solutions.
b) Nitrogen fertilizer solution containers shall be designed to
withstand at least the maximum pressure to which they may be subjected.
c) Containers in excess of 3,000 gallons and designed for 15 psig
or greater shall be constructed in accordance with The Code.
d) Pressure-vented containers not covered by The Code shall be
tested by the manufacturer at one and one-half (1½) times the design working
pressure.
e) Nitrogen fertilizer solution containers of 3,000-gallon
capacity or less shall be clearly and permanently labeled as follows:
1) Name and location of manufacturer.
2) Design pressure (if pressure vented).
f) Nitrogen fertilizer solution containers in excess of 3,000
gallons shall be clearly and permanently labeled as follows:
1) Name and location of manufacturer.
2) Design pressure (if pressure vented).
3) Serial number.
4) Nominal water capacity in U.S. gallons.
5) Year of manufacture.
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.220 CAPACITY OF CONTAINERS
Section 215.220 Capacity of
Containers
Individual container capacity
shall be limited only by good engineering practice (according to The Code).
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.225 CONTAINER VALVES AND ACCESSORIES
Section 215.225 Container
Valves and Accessories
a) Shutoff valves and appurtenances shall be of material suitable
for use with the nitrogen fertilizer solution being handled and designed for
not less than the maximum pressure to which they may be subjected.
b) Except for safety pressure and vacuum relief connections and
vents, connections to pressure-vented containers shall have shutoff valves
located as close to the container as practicable.
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.230 PIPING, TUBING AND FITTINGS
Section 215.230 Piping,
Tubing and Fittings
a) All piping, including tubing, fittings, gaskets, and packing,
shall be made of material suitable for use with nitrogen fertilizer solutions
and designed for the maximum pressure to which they may be subjected.
b) Screwed joints are permissible provided they are able to
withstand maximum pressures to which they are subjected. Pipe joint compounds
shall be resistant to nitrogen fertilizer solutions and compatible with
materials employed.
c) Provisions shall be made in the piping system to compensate
for expansion, contractions, jarring, vibration and settling.
d) After assembly, all piping and tubing shall be tested and
proved to be free from leaks at a pressure not less than the normal operating
pressure of the system. Test procedures shall be conducted in accordance with
the Unfired Pressure Vessel Code of the American Society of Mechanical
Engineers (The Code) and conducted by a person registered with the Society.
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.235 HOSE SPECIFICATIONS
Section 215.235 Hose
Specifications
a) Hose and hose connectors shall be fabricated of materials that
are resistant to the action of the nitrogen fertilizer solution being used.
b) Hose and hose connectors shall be designed for at least the
maximum pressure to which they may be subjected.
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.240 SAFETY DEVICES
Section 215.240 Safety
Devices
a) Every pressure-vented container shall be provided with one or
more safety pressure relief valves. The rate of discharge shall be in
accordance with the provisions of 8 Ill. Adm. Code Section 215.Table E.
b) Container safety pressure relief valves shall be set to
start-to-discharge at a pressure not to exceed 110 percent of the design
pressure of the container.
c) Safety pressure relief valves shall be arranged so the
possibility of tampering will be minimized. If the pressure setting adjustment
is external, the relief valves shall be provided with means for sealing the
adjustment.
d) Shutoff valves shall not be installed between the safety
pressure relief valves or the vacuum relief valve and the container. A safety
relief valve manifold which allows one valve of two, three, four, or more to be
closed and the remaining valve(s) will provide not less than the rate of
discharge to allow the proper cubic feet per minute of air in relation to tank
capacity as shown in 8 Ill. Adm. Code Section 215.Table A.
e) Each safety pressure relief valve and vacuum relief valve used
shall be clearly and permanently marked as follows:
1) The relief setting.
2) The rate of discharge (see 8 Ill. Adm. Code Section 215.Table
E).
3) The manufacturer's name and identification number.
f) Connections for venting, such as couplings, flanges, nozzles,
and discharge lines, to which relief valves are attached, shall have internal
dimensions at least as large in diameter as the relief valve to avoid
restriction of flow through the relief valves.
g) Discharge from safety pressure relief devices of permanent
storage containers shall be directed in such a manner as to prevent any
impingement of escaping gas.
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.245 TRANSFER OF LIQUIDS
Section 215.245 Transfer of
Liquids
a) A competent attendant shall supervise the transfer of liquids
from the time the connections are first made until they are disconnected.
b) Pumps shall be of a material suitable for use with the
solution being handled and designed to withstand the working pressure.
c) Air compressors may be used for transfer of nitrogen
fertilizer solutions.
1) The air compressor shall be protected with a back flow check
valve in the air line to prevent the flow of nitrogen fertilizer solutions or
vapor from the container into the air compressor.
2) A relief valve large enough to discharge the full capacity of
the compressor shall be connected to the discharge before any shutoff valve.
d) All storage installations shall be equipped with devices so as
to minimize tampering while installation is unattended.
e) Containers shall be filled or used only upon authorization of
owner or owner's agent.
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.250 TANK CAR LOADING AND UNLOADING POINTS AND OPERATIONS
Section 215.250 Tank Car
Loading and Unloading Points and Operations
a) A sign reading, "Stop – Tank Car Connected" or
"Stop – Men at Work," shall be displayed at the active end or ends of
the siding while the car is connected for loading or unloading.
b) While tank cars are on siding for loading or unloading, the
wheels at both ends shall be blocked on the rails.
c) Tank car loading or unloading site shall be substantially
level.
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.255 LIQUID LEVEL GAUGING DEVICES
Section 215.255 Liquid Level
Gauging Devices
a) Gauging devices shall be arranged so that the maximum liquid
level to which the container may be filled is readily determinable.
b) Gauging devices shall have a design working pressure at least
equal to the design pressure of the container on which they are used.
c) Tube type liquid level gauging devices on containers in excess
of 3,000 gallons shall be equipped with shutoff valves at the lower connection.
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.260 INDICATING DEVICES
Section 215.260 Indicating
Devices
Because of explosion and extreme
corrosion hazard, no thermometers or other devices containing mercury shall be
used where there is slightest probability of introducing mercury into nitrogen
fertilizer solutions.
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.265 STORAGE INSTALLATIONS FOR NITROGEN FERTILIZER SOLUTIONS
Section 215.265 Storage
Installations for Nitrogen Fertilizer Solutions
a) Location of Storage Containers. Permanent storage shall be
located outside of densely populated areas. If located within the corporate
limits of a village, town or city, written approval of the municipality's
governing body shall be submitted to the Department, accompanied by a plot
plan, drawn to scale, prior to installing said equipment. Storage tanks
installed outside of corporate limits after the effective date of these rules
shall not be less than 10 feet from the lot line of the property that has been
or may be built on or not less than 400 feet from any school, hospital or other
existing places of public and private assembly. A copy of the county's zoning
permit or municipality's approval and plot plan shall be submitted to the
Department prior to site inspection. The Department will approve sites based
upon compliance with this Subpart.
b) Installation of Storage Containers
1) All installation shall be permitted and shall comply with the
requirements of 8 Ill. Adm. Code 255.
2) Aboveground containers shall rest on the ground or on
foundations in such a manner as to permit expansion and contraction. Every
container shall be supported so as to prevent the concentration of excessive
loads on the supporting portion of the shell. That portion of the container in
contact with the foundation or the ground shall be protected against corrosion
in accordance with the Code.
3) Wherever high flood water might occur, the container shall be
securely anchored or placed on a pier of a height above the normal high water
mark.
c) Protection of Storage Containers and Accessories
1) Containers need not be electrically grounded. When an
electrical system exists, such as for lighting or pump motors, the electrical
system shall be installed and grounded as recommended by the National
Electrical Code (January 1, 1982).
2) Storage container sites shall be kept free of debris and
weeds.
3) Information Sign. A sign with letters of a minimum height of
2 inches shall be displayed in a conspicuous place stating the name, address
and telephone number of the owner, manager or local agent of the storage
location.
d) Safety Equipment. All stationary, pressure-vented storage
plants shall have on hand as a minimum the following equipment:
1) A respirator.
2) One pair of rubber or plastic gloves.
3) Readily accessible shower or at least 75 gallons of clean
water in an open top container.
4) Tight-fitting, vent-type chemical goggles or a full face
shield.
e) Transfer of Nitrogen Fertilizer Solutions
1) In the handling and transfer of nitrogen fertilizer solutions
at the storage site, a closed system or an equally effective system that will
control objectionable free vapors shall be provided.
2) Transfer of nitrogen fertilizer solutions from trucks, semi-trailer
or trailers in excess of 3000-gallon capacity shall be made only at sites
approved by the Department (Section 215.255) or at the site of application.
f) Filling Volume. The filling volume of pressure-vented
nitrogen fertilizer solution storage containers shall not exceed 95 percent.
(Source: Amended at 40 Ill. Reg. 8704, effective July 1, 2016)
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.270 SYSTEMS MOUNTED ON TRUCKS, SEMI-TRAILERS AND TRAILERS FOR TRANSPORTATION OF NITROGEN FERTILIZER SOLUTIONS
Section 215.270 Systems
Mounted on Trucks, Semi-trailers and Trailers for Transportation of Nitrogen
Fertilizer Solutions
a) 8 Ill. Adm. Code Section 215.215 applies to this section.
b) Mounting Containers on Trucks.
1) Stops (wood or metal blocks) shall be mounted on the truck,
semi-trailer, trailer, or on the container in such a way that the container
shall not be dislodged from its mounting due to the vehicle coming to a sudden
stop. Back slippage shall also be prevented.
2) Hold-down devices shall anchor the container to the cradle,
frame, or chassis in a manner to prevent the container from rolling or bouncing
off the vehicle and that will not create undue concentration of stress.
3) Any truck or trailer designed so that the container or
containers constitute in whole or part the stress member of the chassis of the
vehicle in lieu of a frame shall be constructed to withstand the additional
stresses which are imposed. Cradles, when welded, shall be welded to the container
by a welder who is registered under The Code and shall be designed to withstand
a force in any direction equal to two (2) times the weight of the container
when filled with nitrogen fertilizer solution.
4) If a liquid withdrawal line is installed in the bottom of a
container, the connections thereto, including hose, shall not be lower than the
lowest horizontal edge of the trailer axle.
5) Both ends of the hose shall be secured while in transit.
6) When the cradle and the tank are not welded together, material
which will not deteriorate with weather or create a friction shall be used
between them to eliminate metal-to-metal friction.
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.275 SYSTEMS MOUNTED ON VEHICLES AND IMPLEMENTS OF HUSBANDRY FOR THE TRANSPORTATION OF NITROGEN FERTILIZER SOLUTIONS
Section 215.275 Systems
Mounted on Vehicles and Implements of Husbandry for the Transportation of
Nitrogen Fertilizer Solutions
a) This section applies to containers of 3,000-gallon capacity or
less and pertinent equipment (piping, valves and gauges attached to the
container) mounted on vehicles and implements of husbandry used for the
transportation of nitrogen fertilizer solutions. 8 Ill. Adm. Code Section
215.215 applies to this section.
b) Mounting Containers.
1) A hold-down device shall be provided which will anchor the
container at one or more places on each side of the container to the vehicle to
prevent its dislodging in event of any sudden stop or start.
2) When containers are mounted on four-wheel trailers, care shall
be taken to insure that the weight is evenly distributed over both axles.
3) When the cradle and the tank are dissimilar metals, material
which will not deteriorate with weather or create friction shall be used
between to eliminate metal-to-metal contact.
c) Container, Valves and Accessories.
1) Each container shall be equipped with a liquid level gauging
device.
2) If a liquid withdrawal line is installed in the bottom of the
container, the connections thereto, including hose, shall not be lower than the
lowest horizontal edge of the vehicle axle.
3) Both ends of the hose shall be secured while in transit.
d) Implements of Husbandry.
1) Implements of husbandry are defined in the Illinois Vehicle
Code, Ch. 95½, Para. 1-130.
2) All trailers shall be securely attached to the vehicle drawing
them supplemented by safety chains of sufficient size and strength to prevent
the towed vehicle parting from the drawing vehicle in the case the drawbar
should break or become disengaged.
3) A trailer shall be constructed so that it will follow in the
path of the towing vehicle and will prevent the towed vehicle from slipping or
swerving dangerously from side to side.
4) All nitrogen fertilizer system vehicles shall carry at least 5
gallons of clean water.
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.280 SYSTEMS MOUNTED ON VEHICLES AND IMPLEMENTS OF HUSBANDRY FOR THE APPLICATION OF NITROGEN FERTILIZER SOLUTIONS
Section 215.280 Systems
Mounted on Vehicles and Implements of Husbandry for the Application of Nitrogen
Fertilizer Solutions
a) Working Pressure and Classifications of Containers.
Containers shall be constructed in accordance with 8 Ill. Adm. Code Section
215.215.
b) Mounting of Containers.
1) Each container shall be supported so as to prevent the
concentration of excessive loads on the supporting portion of the shell.
2) A hold-down device shall be provided which will anchor
container to vehicle at one or more places on each side.
3) When the cradle and the tank are of dissimilar metals,
material which will not deteriorate with weather or create friction shall be
used between to eliminate metal-to-metal contact.
c) Container, Valves and Accessories.
1) Each container shall be equipped with a liquid level gauging
device.
2) Flow control equipment may be connected directly to the tank
coupling or flange, in which case a flexible connection shall be used between
such control equipment and the remainder of the liquid withdrawal system. Flow
control equipment not so installed may be connected to the container with a
flexible connection.
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.285 ADMINISTRATIVE HEARINGS
Section 215.285
Administrative Hearings
Decisions of the Department in
implementing these rules are subject to the Administrative Procedure Act (Ill.
Rev. Stat. 1991, ch. 127, par. 1001-1 et seq.) and the Department's rules
pertaining to administrative hearings as promulgated thereunder (8 Ill. Adm.
Code Part 1).
Section 215.TABLE A Rate of Discharge
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.TABLE A RATE OF DISCHARGE
Section 215.TABLE A Rate of
Discharge
Minimum required rate of
discharge in cubic feet per minute (CFM) of air for safety relief valves.
Discharge measured at 60 degrees F. and atmospheric pressure (14.7 pounds per
square inch).
|
Surface
Area Sq. Ft.
|
CFM
|
Surface
Area Sq. Ft.
|
CFM
|
Surface
Area Sq. Ft.
|
CFM
|
|
|
|
|
|
|
|
|
20
|
258
|
185
|
1,600
|
900
|
5,850
|
|
25
|
310
|
190
|
1,640
|
950
|
6,120
|
|
30
|
360
|
195
|
1,670
|
1,000
|
6,380
|
|
35
|
408
|
200
|
1,710
|
1,050
|
6,640
|
|
40
|
455
|
210
|
1,780
|
1,100
|
6,900
|
|
45
|
501
|
220
|
1,850
|
1,150
|
7,160
|
|
50
|
547
|
230
|
1,920
|
1,200
|
7,410
|
|
55
|
591
|
240
|
1,980
|
1,250
|
7,660
|
|
60
|
635
|
250
|
2,050
|
1,300
|
7,910
|
|
65
|
678
|
260
|
2,120
|
1,350
|
8,160
|
|
70
|
720
|
270
|
2,180
|
1,400
|
8,410
|
|
75
|
762
|
280
|
2,250
|
1,450
|
8,650
|
|
80
|
804
|
290
|
2,320
|
1,500
|
8,900
|
|
85
|
845
|
300
|
2,380
|
1,550
|
9,140
|
|
90
|
885
|
310
|
2,450
|
1,600
|
9,380
|
|
95
|
925
|
320
|
2,510
|
1,650
|
9,620
|
|
100
|
965
|
330
|
2,570
|
1,700
|
9,860
|
|
105
|
1,010
|
340
|
2,640
|
1,750
|
10,090
|
|
110
|
1,050
|
350
|
2,700
|
1,800
|
10,330
|
|
115
|
1,090
|
360
|
2,760
|
1,850
|
10,560
|
|
120
|
1,120
|
370
|
2,830
|
1,900
|
10,800
|
|
125
|
1,160
|
380
|
2,890
|
1,950
|
11,030
|
|
130
|
1,200
|
390
|
2,950
|
2,000
|
11,260
|
|
135
|
1,240
|
400
|
3,010
|
2,050
|
11,490
|
|
140
|
1,280
|
450
|
3,320
|
2,100
|
11,720
|
|
145
|
1,310
|
500
|
3,620
|
2,150
|
11,950
|
|
150
|
1,350
|
550
|
3,910
|
2,200
|
12,180
|
|
155
|
1,390
|
600
|
4,200
|
2,250
|
12,400
|
|
160
|
1,420
|
650
|
4,480
|
2,300
|
12,630
|
|
165
|
1,460
|
700
|
4,760
|
2,350
|
12,850
|
|
170
|
1,500
|
750
|
5,040
|
2,400
|
13,080
|
|
175
|
1,530
|
800
|
5,300
|
2,450
|
13,300
|
|
180
|
1,570
|
850
|
5,590
|
2,500
|
13,520
|
Surface area = Total outside
surface area of container in square feet. When the surface area is not stamped
on the name plate or when the marking is not legible, the area can be
calculated by using one of the following formulas:
a) Cylindrical container with hemispherical heads area = (overall
length in feet times outside diameter in feet times 3.1416)
b) Cylindrical container with semi-ellipsoidal heads. Area =
(overall length in feet plus 0.3 outside diameter in feet) times diameter in
feet times 3.1416.
c) Spherical Container. Area = Outside diameter in feet squared
times 3.1416
Flow Rate SCFM Air = cubic feet
per minute of air required at standard conditions, 60 degrees F. and
atmospheric pressure (14.7 psia).
The rate of discharge may be
interpolated for intermediate values of surface area. For container with total
outside surface area greater than 2,000 sq. ft., the required flow rate can be
calculated using the formula, Flow Rate SCFM Air = 22.11A degrees .82, where A=
outside surface area of the container in square feet.
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.TABLE B GUIDE FOR SELECTION OF MATERIALS FOR REFRIGERATED AMMONIA STORAGE TANKS
Section 215.TABLE B Guide
for Selection of Materials for Refrigerated Ammonia Storage Tanks
a) Materials for shell and bottom for tanks of all design
pressures shall have ductility at low temperatures equal to or superior to
those listed in 8 Ill. Adm. Code Section 215.Table C.
b) When austenitic steels or non-ferrous materials are used, the
Code shall be used as a guide for temperature requirements.
c) Materials for nozzles, attached flanges, structural members
which are in tension, and other such critical elements shall be selected for
the design temperature. This selection shall be based on impact test
requirements, or on probabilites such as used for the plate materials listed in
8 Ill. Adm. Code Section 215.Table C.
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.TABLE C MINIMUM MATERIAL REQUIREMENTS FOR SHELLS AND BOTTOMS OF REFRIGERATED STORAGE TANKS FOR VARIOUS TEMPERATURES AND THICKNESSES
Section 215.TABLE C Minimum
Material Requirements for Shells and Bottoms of Refrigerated Storage Tanks for
Various Temperatures and Thicknesses
|
Design Temperature
|
Thickness
|
Material Spec.
|
Qualifications to be Added to the
Basic Specification
|
|
|
|
|
|
|
|
|
|
|
|
65 F to 25 F, incl. (See Note
1)
|
Up to ½", incl.
|
Any approved steel with
specified min. T.S. not exceeding 60,000 psi
|
None
|
|
|
|
|
|
|
|
|
|
Over ½" to 1", incl.
|
A-131B (or C)
|
None
|
|
|
Case 1256
|
None
|
|
|
A-201 A & B
|
FGP (Fine grain practice)
|
|
|
|
|
|
|
|
|
|
Over 1" to 1⅜",
incl.
|
A-131C, Case 1256-
|
None
|
|
|
|
|
A-201 A & B
|
None
|
|
|
|
|
|
FGP
|
|
|
.
|
|
|
|
|
|
|
Over 1⅜"
|
A-131C
|
Normalized
|
|
|
|
|
Case 1256
|
Normalized
|
|
|
|
|
A-201 A & B
|
FGP, Normalized
|
|
|
|
|
|
|
|
|
Below 25 F to 5 F, incl. (See
Note 2)
|
Up to ½", incl.
|
Case 1256
|
None
|
|
|
A-201 A & B
|
None
|
|
|
|
|
|
|
|
Over ½" to 1⅜
", incl.
|
A-131B (to 1" max.)
|
FGP
|
|
|
|
|
A-131C
|
FGP
|
|
|
|
|
Case 1256
|
FGP
|
|
|
|
|
A-201 A & B (to 1"
max)
|
FGP, High Mang.*
|
|
|
|
|
A-201 A & B (over 1")
|
FGP, High Mang., Normalized
|
|
|
|
|
|
|
|
|
|
Over 1⅜ "
|
A-131C
|
Normalized
|
|
|
|
|
Case 1256
|
Normalized
|
|
|
|
|
A-201 A & B
|
FGP, High Mang., Normalized
|
|
|
|
|
|
|
|
|
Below -5F to -30F (See Note 3)
|
Up to ½" incl.
|
Case 1256
|
FGP
|
|
|
A-201 A & B
|
FGP, High Mang.
|
|
|
|
|
|
|
|
|
|
Over ½" to 1⅜"
incl.
|
A-131B (to 1" max)
|
FGP, Normalized
|
|
|
|
|
A-131C
|
Normalized
|
|
|
|
|
Case 1256
|
FGP, Normalized
|
|
|
|
|
A-201 A & B
|
FGP, High Mang., Normalized
|
|
|
|
|
|
|
|
|
|
Over 1⅜"
|
A-300 Class 1
|
A-201 A & B only
|
|
*Manganese content of 0.70% to
1.0% is preferred in lieu of usual content of 0.80% maximum.
Note 1: The design
temperature shall be taken as the lower of the following:
a) The minimum temperature to which the tank contents will be
refrigerated.
b) The minimum estimated tank shell temperature due to atmospheric
temperatures, considering the effectiveness of the insulation in keeping shell
temperatures above expected minimum atmospheric temperature (if expected to be
below the refrigerated temperature).
Note 2: For this thickness,
temperature category approved steels include all those listed in API 12-C and
API 620. Materials for vessels must comply with requirements of the Code and
any additional requirements of this table. A-131 steel is not approved by ASME
and some Code cases have not been approved by local jurisdictions. All
specific materials listed in table are satisfactory for all designs based on
API 12-C or API 620.
Note 3: For vessels constructed
under the Code with a design temperature below -20F., the impact requirements
shall comply with 8 Ill. Adm. Code Section 215.Table B.
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.TABLE D REPAIR WELDING
Section 215.TABLE D Repair
Welding
a) All containers, piping and appurtenances which have contained
or have been in direct contact with nitrogen fertilizer solutions containing
ammonium nitrate must be thoroughly cleaned and washed with water (or steam) to
eliminate all solid ammonium nitrate before welding or torch cutting may be
attemped. Extreme caution should be taken before attempting to weld or torch
cut any container when ammonium nitrate could be trapped, for example, in the
area between tank shell and a reinforcing plate.
b) All containers, piping, and appurtenances which have contained
aqua ammonia (ammonium hydroxide) must be thoroughly vented and thoroughly
washed with large quantities of water. After washing, they shall be filled
with water to a level higher than area to be welded or repaired.
c) All containers shall be welded in accordance with the Code.
 | TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE SUBCHAPTER e: FERTILIZERS
PART 215
ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS,
EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.TABLE E SAFETY PRESSURE RELIEF VALVES
Section 215.TABLE E Safety
Pressure Relief Valves
a) The rate of discharge shall be stamped on the safety relief
valve in cubic feet of air per minute at:
1) 60 degrees F.,
2) 14.7 pounds per square inch absolute, and
3) 120 percent of the stamped start-to-discharge setting.
b) Safety pressure relief valves in systems utilizing air
compressors for the transfer of nitrogen fertilizer solutions shall have a
minimum rate of discharge in cubic feet per minute of air of 120 percent of the
compressor manufacturer's maximum rated capacity.
c) Safety pressure relief valves in systems utilizing pumps for
transfer of nitrogen fertilizer solutions shall have a minimum rate of
discharge of 120 percent of the liquid inflow rate. This can be computed as
follows: Liquid pump maximum rated capacity in GPM times 0.16 equals vapor
flow in CFM.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|