a) Single Bathroom Groups. A single bathroom group of fixtures may be installed with the drain from an individually vented lavatory or kitchen sink or a kitchen sink serving as a wet vent for a bathtub or shower and for the water closet, provided that:
1) Not more than 4 drainage fixture units drain into a 2 inch diameter wet vent; and
2) The horizontal branch shall be a minimum of 2 inches and connect to the stack at the same level as the water closet drain. It may also connect to the water closet bend. (See Appendix K: Illustration S.)
b) Double Bathroom Groups. Bathroom groups back-to-back on the top floor consisting of 2 lavatories and 2 bathtubs or showers may be installed on the same horizontal branch with a common vent for the lavatories and with no individual vent for bathtubs or showers, provided the wet vent is 2 inches in diameter, and the length of the fixture drain conforms to Appendix A: Table E. (See Appendix K: Illustration T.)
c) Multi-story Bathroom Groups. On the lower floors of a multi-story building, the waste pipe from one or 2 lavatories may be used as a wet vent for one or 2 bathtubs or showers, provided that:
1) The wet vent and its extension to the vent stack is 2 inches in diameter;
2) Each water closet below the top floor is back-vented; and
3) The vent stack is sized as given in Appendix A: Table J. (See Appendix K: Illustrations U and V.)