TITLE 35: ENVIRONMENTAL PROTECTION
SUBTITLE C: WATER POLLUTION CHAPTER I: POLLUTION CONTROL BOARD PART 304 EFFLUENT STANDARDS SECTION 304.222 INTERMITTENT DISCHARGE OF TRC
Section 304.222 Intermittent Discharge of TRC
The acute TRC water quality standard of 35 Ill. Adm. Code 302.208 and 302.504(a) by operation of Section 304.105 shall not apply to any discharge which contains TRC solely as the result of intermittent usage for antifouling purposes related to the operation of condensers and cooling systems. For the purposes of this Section usage of chlorine or related substances measureable as TRC shall be deemed to be intermittent if usage is restricted to a maximum of two hours per day per condenser or cooling system unit. Discharge concentration of TRC averaged or composited over the discharge period shall not exceed 0.2 mg/l nor shall the TRC concentration exceed 0.5 mg/l at any time.
(Source: Amended at 22 Ill. Reg. 1351, effective December 24, 1997) |