TITLE 32: ENERGY
CHAPTER II: ILLINOIS EMERGENCY MANAGEMENT AGENCY SUBCHAPTER b: RADIATION PROTECTION PART 340 STANDARDS FOR PROTECTION AGAINST RADIATION SECTION 340.830 CONTROL OF VOLATILES AND GASES
Section 340.830 Control of Volatiles and Gases
a) A licensee who uses or stores radioactive volatile materials or gases shall do so with a system that will keep airborne concentrations within the limits prescribed in this Part.
b) The system shall either be directly vented to the atmosphere through an air exhaust or provide for collection and decay or disposal of the volatile material or gas in a shielded container.
c) A licensee shall use or store radioactive gases only in rooms that are at negative pressure compared to surrounding rooms or hallways.
d) A licensee shall post, at the area of use or storage, emergency procedures to be followed in the event of a gas spill.
e) In the event of evacuation because of a spill or leak, the licensee shall use a radiation detection survey instrument upon room re-entry to ensure radiation levels have returned to background levels.
f) A licensee shall check the operation of reusable collection systems monthly and measure the ventilation rates available in areas of use at intervals not to exceed 6 months. The licensee shall maintain a record of these checks for 5 years. The record shall include the model and serial number of the collection system, results of all checks recommended by the manufacturer of the collection system, the date of the checks and the identity of the individual who performed the checks.
g) Contaminated charcoal trap filters, air handling systems and respiratory equipment shall be disposed of in accordance with this Part.
(Source: Added at 29 Ill. Reg. 20841, effective December 16, 2005) |